ThermiStar L .. SP 01/03/10
6. Assembly
33
WARNING!
Risk of life through fire!
Easily flammable materials or liquids can catch fire.
Therefore:
-
Do not use or store explosive or easily flammable
substances (i.e. fuel, paints, paper, wood) in the
area where the device is installed.
-
Do not dry or store laundry or clothes in the area
where the device is installed.
-
Do not operate device in explosive atmosphere un-
der any circumstances.
The following aspects must be taken into consideration already
during the planning of the system, in addition to proper
dimensioning:
-
Future location of the heat pump under the aspect of sound
transmission through air and structure-borne sound. The acoustics
in the erection rooms with reverberating walls can increase the
operating sound significantly. Countermeasure: acoustic insulation
on one of the opposite wall or ceiling surfaces.
-
To reduce the structure-borne sound transmission, create a
separate pedestal (e.g. heavy concrete) in mounted in floating
fashion (e.g. on rubber).
-
A pedestal is recommended for easier maintenance and care.
NOTE!
MHG Heiztechnik recommends the installation of an
oil sump-pump especially if the condenser is located
shut off in a room for several hours (below 12 °C) and
it becomes colder than the evaporator. This condition
can occur especially in combination with special
solar systems.
NOTE!
Thorough planning with adequately dimensioned
heat source is especially important for reasons of
operational reliability and improved working output.
NOTE!
If these comments are disregarded, the warranty
becomes void in case of damages that can be traced
to one of these causes.
Application limits
Heating water 20-55°C with refrigerant R 407 C
Installation clearances
Min. clearances according to Fig. 3 must be observed to allow all
work activities (assembly, startup, maintenance) to be performed
unhampered.
-
Observe the lateral clearance to the heat pump (min. 20 cm) to
allow access for service and inspection.
Содержание 98.30000-6324
Страница 1: ...ThermiStar L SP 01 03 10 ...
Страница 18: ...5 Technical Data ThermiStar L SP 01 03 10 18 5 2 Type plate Fig 4 Sample type plate ...
Страница 21: ...ThermiStar L SP 01 03 10 5 Technical Data 21 ...
Страница 39: ...ThermiStar L SP 01 03 10 6 Assembly 39 Fig 11 Sensor cable heat source intake 5 ...
Страница 68: ...8 Maintenance ThermiStar L SP 01 03 10 68 8 4 Spare part drawing and legend Fig 40 ...
Страница 88: ...Your notes ThermiStar L SP 01 03 10 88 ...
Страница 89: ...ThermiStar L SP 01 03 10 Your notes 89 ...
Страница 90: ...Your notes ThermiStar L SP 01 03 10 90 ...
Страница 92: ......