ThermiStar L .. SP 01/03/10
6. Assembly
45
6.5 Hydraulic
connection
Requirements on the heating water
To prevent corrosion damages in the heating system, heating water
in potable quality must be used under consideration of the
requirements according to VDI guideline 2035 "Preventing damages
in warm water heating systems".
CAUTION!
Device damages through dirt or contamination!
Partial clogging in the heat exchanger can lead to its
destruction.
Therefore:
-
For installations in older systems pre-filtration/silt
separation must be installed in order to protect the
plate heat exchanger.
Do not use any chemical additives!
Fig. 17:
Hydraulic connections
Legend for Fig. 17:
Abbr.
Meaning
1
Flow
2
Return
Verify correct flow direction when connecting the hydraulic line. At
the condenser, the in-flow is at the bottom (heating water return to
heat pump). It is important with the hydraulic connection to observe
the correct directions of flow. For the condenser the flow occurs at
the bottom (return of heating water to heat pump).
The temperature spread of 3-4 K at the heat source and 5-10 K
at the heat drop must be maintained under normal operating
conditions while observing the application limits. This spread is
normally achieved when the volume flows specified in the technical
data are observed.
Содержание 98.30000-6324
Страница 1: ...ThermiStar L SP 01 03 10 ...
Страница 18: ...5 Technical Data ThermiStar L SP 01 03 10 18 5 2 Type plate Fig 4 Sample type plate ...
Страница 21: ...ThermiStar L SP 01 03 10 5 Technical Data 21 ...
Страница 39: ...ThermiStar L SP 01 03 10 6 Assembly 39 Fig 11 Sensor cable heat source intake 5 ...
Страница 68: ...8 Maintenance ThermiStar L SP 01 03 10 68 8 4 Spare part drawing and legend Fig 40 ...
Страница 88: ...Your notes ThermiStar L SP 01 03 10 88 ...
Страница 89: ...ThermiStar L SP 01 03 10 Your notes 89 ...
Страница 90: ...Your notes ThermiStar L SP 01 03 10 90 ...
Страница 92: ......