ThermiStar L .. SP 01/03/10
8. Maintenance
63
8.2
Components relevant to
safety
To ensure the long-term availability and safety of heat generators
and components and to meet the requirements of the EU guideline
2002/91/EG, the following components must be replaced after they
have reached the nominal service life, specified by the manufacturer
in terms of time or switching cycles. With modern devices, the
switching cycles can usually read on a display/indicator. In cases
where the switching cycle cannot be read, the time is relevant for
the replacement.
Nominal service life of heat
generator components
Components relevant to safety
Time [a]
Switching
cycles [-]
Regulation 10
250.000
Pressure relief valves
10
n.a.
List of typical wearing parts
The wearing parts are regularly inspected by the trained technician
during service activities and replaced, if necessary.
Wearing parts
Replacement intervals / Years
(non-binding factory
recommendation)
Sealing rings / rubber thrust
collars
2
Sealing ropes
2
Temperature control devices
5
Содержание 98.30000-6324
Страница 1: ...ThermiStar L SP 01 03 10 ...
Страница 18: ...5 Technical Data ThermiStar L SP 01 03 10 18 5 2 Type plate Fig 4 Sample type plate ...
Страница 21: ...ThermiStar L SP 01 03 10 5 Technical Data 21 ...
Страница 39: ...ThermiStar L SP 01 03 10 6 Assembly 39 Fig 11 Sensor cable heat source intake 5 ...
Страница 68: ...8 Maintenance ThermiStar L SP 01 03 10 68 8 4 Spare part drawing and legend Fig 40 ...
Страница 88: ...Your notes ThermiStar L SP 01 03 10 88 ...
Страница 89: ...ThermiStar L SP 01 03 10 Your notes 89 ...
Страница 90: ...Your notes ThermiStar L SP 01 03 10 90 ...
Страница 92: ......