ThermiStar L .. SP 01/03/10
5. Technical Data
31
Interfaces
BSB
Max. line length
Basic unit - peripheral unit
Max. total line length
Min. wire gauge
2-wire connection, not interchangeable
200 m
400 m (Max. cable capacity: 60 nF)
0.5 mm
2
LPB
with controller bus feed (per controller)
with central bus feed
bus load number
Cu cable 1.5 mm2, 2-wire, not interchangeable
250 m
460 m
E = 3
Standards,
Safety, EMC
etc.
CE conformity according to
EMC guideline
- Electromagnetic immunity
- Emissions
Low-voltage
guideline
- electrical safety
2004/108/EC
- EN 61000-6-2
- EN 61000-6-3
2006/95/EC
- EN 60730-1, EN 60730-2-9