4.2.2
Operation with the Normal AC Source Down
In the event of a normal AC source failure or voltage outside specified tolerances of ±10% in amplitude (±15%
optionally), the rectifier/charger
(A)
stops and the battery
(D)
supplies the necessary backup power to the load via
the inverter
(B)
.
The battery, float-connected between the rectifier/charger and the inverter, discharges during this operating mode:
◗
lights
2
,
4
and
5
shine green.
The user is warned of battery operation by the slow beeping of the buzzer
6
, see Figure 4-6, and the message
"LOAD PROTECTED, BATTERY DISCHARGING", followed by the remaining backup time and the percent load.
This information is also available via volt-free changeover contacts for remote control devices.
Figure 4-6: Normal AC Source Indicator Diagram.
2
1
4
5
2
1
2
AB
C
D
Galaxy PW
™
UPS 100 to 225kVA
Operation
4 — 4
86-133060-00 A00
Содержание GALAXY PW 100
Страница 6: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA vi 86 133060 00 A00...
Страница 22: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA Introduction 1 10 86 133060 00 A00...
Страница 34: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA 2 12 86 133060 00 A00...
Страница 78: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA 5 8 86 133060 00 A00...
Страница 88: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA Appendices A 10 86 133060 00 A00...
Страница 90: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA Appendices A 12 86 133060 00 A00...
Страница 92: ...This page left blank intentionally Galaxy PWTM UPS 100 to 225 kVA A 14 86 133060 00 A00...
Страница 94: ...Galaxy PWTM UPS 100 to 225 kVA 86 133060 00 A00...
Страница 96: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA W 4 86 133060 00 A00...
Страница 100: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA G 4 86 133060 00 A00...
Страница 102: ......
Страница 103: ......