Installation and User Manual
3.8.1
"Temperature Monitor" installation in a Battery Room
The "Temperature Monitor" should be secured against a wall or any vertical support. See Figure 3-10.
1.
Choose a location near the batteries and away from draughts which adversely affect the accuracy of
temperature measurements. Dimensions: 75 x 75 x 21 mm.
2.
Use the holes provided in the base plate to screw the unit to the vertical support, unless the connecting cable
runs on the surface, break the knock-out in the unit base plate provided for cable entry. Secure the cable by
suitable means so that it does not pull on the unit.
Figure 3-10: Temperature Monitor" Base.
Mounting Hole
Cable Entry
Mounting Hole
Dimensions: 75 x 75 x 21 mm
board
Installation
3 — 11
86-133060-00 A00
Содержание GALAXY PW 100
Страница 6: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA vi 86 133060 00 A00...
Страница 22: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA Introduction 1 10 86 133060 00 A00...
Страница 34: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA 2 12 86 133060 00 A00...
Страница 78: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA 5 8 86 133060 00 A00...
Страница 88: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA Appendices A 10 86 133060 00 A00...
Страница 90: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA Appendices A 12 86 133060 00 A00...
Страница 92: ...This page left blank intentionally Galaxy PWTM UPS 100 to 225 kVA A 14 86 133060 00 A00...
Страница 94: ...Galaxy PWTM UPS 100 to 225 kVA 86 133060 00 A00...
Страница 96: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA W 4 86 133060 00 A00...
Страница 100: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA G 4 86 133060 00 A00...
Страница 102: ......
Страница 103: ......