1.6
Electrical Parameters for Selecting Protective Devices
1.6.1 Normal
AC
Source
The parameters given in Table 1-1 can be used to determine the required rating of the upstream protective circuit
breaker on the normal AC input for one single-UPS or parallel-UPS unit.
Normal and Bypass AC Input:
number of conductors
3 phases
rated voltage and tolerances
480 V ± 10% (adjustable to ± 15%)
rated frequency and tolerances
60 Hz / ± 10%
IMPORTANT
It is essential to choose the type of circuit breaker according to its breaking
capacity and the prospective short-circuit current at its place of installation.
This choice must also be made so as to protect the static-switch semicon-
ductors with respect to the maximum permissible currents and ensure
discrimination between the UPS output fuses and the downstream
protection devices.
Table 1-1: Electrical Parameters for Normal AC Source.
Electrical parameters for the normal AC source
rated
current normal AC source
UPS
rated current In for unit:
for 25%
for 50%
output
with battery at start
without battery (2)
overload (3)
overload (3)
in kVA
of charge cycle (1)
100
166
159
199
239
130
214
205
256
308
150
245
236
295
354
180
295
283
354
425
200
328
316
395
474
225
332
320
400
480
(1)
The rated normal AC source currents (In) have been determined for a rated phase-to-phase voltage of 480 V,
a battery with a 10 minute backup time at the beginning of its charge (412 x 1, 2 = 494 Volts) and full rated load
with a power factor of 0.9.
(2)
The rated normal AC source currents (In) have been determined for float charging voltage and full rated load
with a power factor of 0.9
(3)
The normal AC source currents given for an overload of 25% or 50% are maximum values. They have been
determined for a battery with float charging voltage and a load power factor of 0.9. When choosing the circuit
breaker rating, use the "rated current" column and check that the circuit breaker tripping curves are compatible
with the values in the overload columns.
Galaxy PW
™
UPS 100 to 225kVA
Introduction
1 — 6
86-133060-00 A00
Содержание GALAXY PW 100
Страница 6: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA vi 86 133060 00 A00...
Страница 22: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA Introduction 1 10 86 133060 00 A00...
Страница 34: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA 2 12 86 133060 00 A00...
Страница 78: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA 5 8 86 133060 00 A00...
Страница 88: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA Appendices A 10 86 133060 00 A00...
Страница 90: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA Appendices A 12 86 133060 00 A00...
Страница 92: ...This page left blank intentionally Galaxy PWTM UPS 100 to 225 kVA A 14 86 133060 00 A00...
Страница 94: ...Galaxy PWTM UPS 100 to 225 kVA 86 133060 00 A00...
Страница 96: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA W 4 86 133060 00 A00...
Страница 100: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA G 4 86 133060 00 A00...
Страница 102: ......
Страница 103: ......