![MGE UPS Systems GALAXY PW 100 Скачать руководство пользователя страница 32](http://html1.mh-extra.com/html/mge-ups-systems/galaxy-pw-100/galaxy-pw-100_installation-and-user-manual_1783083032.webp)
2.7
System Start-up
2.7.1
Single UPS unit or Redundant Parallel UPS
Proceed in the following order: See Figure 2-7.
1.
Close the upstream switches supplying normal and bypass AC source power (on the LV switchboard).
2.
Close normal AC input switch Q1. The system powers up:
- the rectifier/charger automatically starts.
- green light
1
on the control panel goes on.
- light
2
turns red.
3.
Close bypass AC input switch Q4S:
- green lights
3
and
5
on the control panel go on.
4.
Close inverter output switch Q5N.
5.
Close battery circuit breaker QF1:
- light
2
goes off.
6.
Open maintenance bypass switch Q3BP.
7.
Press the "inverter on" button
7
on the control panel:
- the green "inverter" light
4
flashes.
- the inverter starts, then, if the bypass AC source transfer conditions are satisfied, the load is transferred
to the inverter if the on-line mode is selected.
- the green "static-bypass" light
3
goes off.
- the green "inverter" light
4
shines for on-line mode.
Figure 2-7: Single UPS Unit Start-up Diagram.
Q5N
Q1
Q4S
QF1
0
I
3
1
2
1
0
1
0
1
0
1
0
1
0
Q3BP
1
0
1
0
1
0
1
0
1
0
1
0
1
0
5
4
6
1
0
1
0
1
0
1
0
7
8
1
2
8
7
6
4
3
5
2
1
22
Galaxy PW
™
UPS 100 to 225kVA
System Setup
2 — 10
86-133060-00 A00
Содержание GALAXY PW 100
Страница 6: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA vi 86 133060 00 A00...
Страница 22: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA Introduction 1 10 86 133060 00 A00...
Страница 34: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA 2 12 86 133060 00 A00...
Страница 78: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA 5 8 86 133060 00 A00...
Страница 88: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA Appendices A 10 86 133060 00 A00...
Страница 90: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA Appendices A 12 86 133060 00 A00...
Страница 92: ...This page left blank intentionally Galaxy PWTM UPS 100 to 225 kVA A 14 86 133060 00 A00...
Страница 94: ...Galaxy PWTM UPS 100 to 225 kVA 86 133060 00 A00...
Страница 96: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA W 4 86 133060 00 A00...
Страница 100: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA G 4 86 133060 00 A00...
Страница 102: ......
Страница 103: ......