1.5
System Specifications
1.5.1
Electrical Characteristics
Installation and User Manual
Introduction
1 — 5
86-133060-00 A00
UPS power rating in kVA
100
130
150
180
200
225
Normal AC input
number of conductors
3 phases
rated voltage and tolerances
480 V ± 10% (adjustable to ± 15%)
rated frequency and tolerances
60 Hz / ± 10%
THDI
< 14%
< 11%
< 10%
< 8%
< 7.6%
< 7.5%
power factor
up to 0.9
Bypass AC input
number of conductors
3 phases 3 neutral
rated voltage and tolerances
480 V / ± 10%
rated frequency and tolerances
60 Hz / ± 10%
Load
number of conductors
3 phases 3 neutral
Ph/Ph voltages
480 V
Ph/N voltages
277 V
voltage fluctuations (Ph/Ph,Ph/N)
± 1%
adjustable frequency and tolerances
(on battery power)
60 Hz ± 0.05 Hz
synchronization with bypass
± 0.5 Hz (adjustable from ± 0.25 Hz to ± 2 Hz)
transient voltage variation for 0 to 100% load step change
± 2% (with battery), +2%/-6% (without battery)
permissible overloads
150% for 1 minute, 125% for 10 minutes
Isc Ph/Ph (% of I rated)
4.7
3.6
3.2
2.6
2.4
2.1
Isc Ph/N (% of I rated)
7.4
5.7
5
4.1
3.7
3.3
THDU Ph/Ph and Ph/N for linear load
< 1.5% Ph/Ph, < 2% Ph/N
THDU Ph/Ph and Ph/N for non-linear load
< 2% Ph/Ph, < 3% Ph/N
(at 80% of Pn)
Battery
voltage floating
512V to 561V
standard battery type
gas-recombination sealed lead-acid battery
UPS characteristics
active power (kW)
100
130
150
180
200
202.5*
efficiency at 50% load (%)
90.5
91
92
92.5
92.5
93
(values ± 1%)
efficiency at 100% load (%)
92.5
93
93
93
93.5
93.5
(values ± 1%)
heat losses
(1)
in KW
8.1
9.8
11.3
13.5
13.9
14.1
in cal./s
1940
2350
2700
3240
3340
3380
storage temperature range ºF (ºC)
-13 to 158 (-25 to 70) dry heat — unit without battery
-4 to 113 (-20 to 45) — unit with battery
operating temperature range ºF (ºC)
32 to 95, 104 for 8 hours (0 to 35, 40 for 8 hours)
relative humidity
95% maximum non condensing at ambient temperature
maximum operating altitude without derating, FT(m)
< 3280 (< 1000)
noise level (dBA)
62
63
64
65
67
68
dimensions, in. (mm)
width
47.8 (1215)
depth
33 (840)
height
74.8 ± .39 (1900 ± 10)
weight lbs (kg)
3050 (1388)
standards
design
NFPA / NEC / NEMA / OSMA
product and safety
UL 1778 - ULC
electromagnetic compatibility
FCC Part 15, Subport J, Class A - IEEE587 / ANSI 62.41
(1)
: The losses indicated are those produced at full rated load with the battery float charging. They must be taken into account when sizing the ventilation system.
* pf of 225kVA unit has 0.9 and remaining units have 1.0.
Содержание GALAXY PW 100
Страница 6: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA vi 86 133060 00 A00...
Страница 22: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA Introduction 1 10 86 133060 00 A00...
Страница 34: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA 2 12 86 133060 00 A00...
Страница 78: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA 5 8 86 133060 00 A00...
Страница 88: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA Appendices A 10 86 133060 00 A00...
Страница 90: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA Appendices A 12 86 133060 00 A00...
Страница 92: ...This page left blank intentionally Galaxy PWTM UPS 100 to 225 kVA A 14 86 133060 00 A00...
Страница 94: ...Galaxy PWTM UPS 100 to 225 kVA 86 133060 00 A00...
Страница 96: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA W 4 86 133060 00 A00...
Страница 100: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA G 4 86 133060 00 A00...
Страница 102: ......
Страница 103: ......