![MGE UPS Systems GALAXY PW 100 Скачать руководство пользователя страница 25](http://html1.mh-extra.com/html/mge-ups-systems/galaxy-pw-100/galaxy-pw-100_installation-and-user-manual_1783083025.webp)
Installation and User Manual
Figure 2-1: Handling Cabinet From the Bottom or Rolling on Bars.
2.1.2
Storage
The equipment must be stored in a dry and well-aired location, sheltered from rain, water sprays or splashes and
all chemical agents. Storage in original packing is recommended, since this packaging is designed to provide
maximum protection during storage and handling. If the unit must be unpacked prior to final installation, cover the
equipment with a shroud providing protection against dust, debris, or paint.
Please dispose of the packaging in accordance with the applicable legislation.
IMPORTANT
Transport: the temperatures must remain within the -30° to +50°C range and the
duration should not exceed 30 days.
Storage: the battery is of the sealed lead-acid or vented lead-acid type and should not be stored for more than six
months at 20°C without recharging for batteries that are initially fully charged (for partially charged batteries, the
storage time should be reduced). After the recommended maximum storage time, the battery must be charged,
requiring partial start-up of the equipment (rectifier-charger).
The battery cells can be stored at a temperature between -20°C and +45°C if delivered in their initial packing.
The ideal battery storage temperature is between 15° and 25°C (higher temperatures result in reduced storage life
or downgraded technical characteristics). If higher temperatures cannot be avoided during transport or storage,
please consult us.
System Setup
2 — 3
86-133060-00 A00
A
From Bottom
B
On Rollers
Содержание GALAXY PW 100
Страница 6: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA vi 86 133060 00 A00...
Страница 22: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA Introduction 1 10 86 133060 00 A00...
Страница 34: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA 2 12 86 133060 00 A00...
Страница 78: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA 5 8 86 133060 00 A00...
Страница 88: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA Appendices A 10 86 133060 00 A00...
Страница 90: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA Appendices A 12 86 133060 00 A00...
Страница 92: ...This page left blank intentionally Galaxy PWTM UPS 100 to 225 kVA A 14 86 133060 00 A00...
Страница 94: ...Galaxy PWTM UPS 100 to 225 kVA 86 133060 00 A00...
Страница 96: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA W 4 86 133060 00 A00...
Страница 100: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA G 4 86 133060 00 A00...
Страница 102: ......
Страница 103: ......