Installation and User Manual
1.8
Parallel Connected UPS Units
For installations with redundant units, take into account only the units required to supply the load power (e.g. for an
installation made up of 3 parallel-connected UPS units, one being redundant, only 2 UPS units are used to
determine bypass AC source and load currents and cable cross-sections).
Table 1-5 serves as an example for a parallel connected installation comprising up to four UPS units.
Table 1-5: Parameters for Bypass AC Source and Load Cables for a Parallel UPS.
Parameters
rated unit
number of
total UPS
bypass AC
output
parallel-
rated output
source or load
in kVA
connected
in kVA
line current
units
in Amps
100
2
200
240
3
300
360
4
400
480
130
2
260
312
3
390
468
4
520
624
150
2
300
360
3
450
540
4
600
720
180
2
360
434
3
540
651
4
720
868
200
2
400
482
3
600
723
4
800
964
225
2
450
542
3
675
813
4
900
1084
Introduction
1 — 9
86-133060-00 A00
Содержание GALAXY PW 100
Страница 6: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA vi 86 133060 00 A00...
Страница 22: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA Introduction 1 10 86 133060 00 A00...
Страница 34: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA 2 12 86 133060 00 A00...
Страница 78: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA 5 8 86 133060 00 A00...
Страница 88: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA Appendices A 10 86 133060 00 A00...
Страница 90: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA Appendices A 12 86 133060 00 A00...
Страница 92: ...This page left blank intentionally Galaxy PWTM UPS 100 to 225 kVA A 14 86 133060 00 A00...
Страница 94: ...Galaxy PWTM UPS 100 to 225 kVA 86 133060 00 A00...
Страница 96: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA W 4 86 133060 00 A00...
Страница 100: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA G 4 86 133060 00 A00...
Страница 102: ......
Страница 103: ......