Installation and User Manual
1.6.2
Bypass AC Source
The parameters given in Table 1-2 and 1-2A can be used to determine the required rating of the upstream protec-
tive circuit breaker on bypass AC input.
NOTE
If the installation includes a transformer on the bypass AC input, allow for the
inrush current caused by magnetization of the transformer windings.
Table 1-2: Electrical Parameters for Bypass AC Source.
Electrical parameters for bypass AC source (480 V)
rated UPS
current bypass AC source (1)
output
rated current In for unit:
for 25%
for 50%
in kVA
overload
overload (3)
100
120
150
180
130
156
205
234
150
180
236
270
180
217
283
325
200
241
316
362
225
271
320
407
(1)
The bypass AC source currents have been determined for a rated phase-to-phase voltage of 480 V, a load
power factor of 0.9 and for full rated load as well as overloads of 25% or 50%. When choosing the circuit breaker
rating, use the "rated current" column and check that the circuit breaker tripping curves are compatible with the
data in the overload columns. See table and chart below.
Table 1-2A:
UPS output
maximum permissible current
in kVA
100
50 In for 20 ms
130
38 In for 20 ms
150
33 In for 20 ms
180
27 In for 20 ms
200
25 In for 20 ms
225
22 In for 20 ms
Figure 1-3: Fuse Curve Chart.
10
4
t(s)
I(A)
10
3
10
2
10
1
1
10-
1
10-
4
10-
3
10-
2
10
2
10
3
10
4
Introduction
1 — 7
86-133060-00 A00
Содержание GALAXY PW 100
Страница 6: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA vi 86 133060 00 A00...
Страница 22: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA Introduction 1 10 86 133060 00 A00...
Страница 34: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA 2 12 86 133060 00 A00...
Страница 78: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA 5 8 86 133060 00 A00...
Страница 88: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA Appendices A 10 86 133060 00 A00...
Страница 90: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA Appendices A 12 86 133060 00 A00...
Страница 92: ...This page left blank intentionally Galaxy PWTM UPS 100 to 225 kVA A 14 86 133060 00 A00...
Страница 94: ...Galaxy PWTM UPS 100 to 225 kVA 86 133060 00 A00...
Страница 96: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA W 4 86 133060 00 A00...
Страница 100: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA G 4 86 133060 00 A00...
Страница 102: ......
Страница 103: ......