Current
Table 19 Current boundary limits slave BMS
Boundary condition
Name
Level
Default
Performance
Time
Charging over current warning
Set
> 1.5C
> 2C
10 sec.
Clear
<= 1.5C
<= 2C
10 sec.
Charging over current critical
Failsafe
> 2.4C
+20 sec.
Discharging over current warning
Set
> 2.0C
> 3C
10 sec.
Clear
<= 2.0C
<= 3C
10 sec.
Balancing
Table 20 Balancing boundary limits slave BMS
Boundary condition
Name
Level
Default
Performance
Time
Offset cell voltage
> 5 mV
5 min.
Balancing cell voltage
>= 3855 mV
>= 3905 mV
5 min.
Battery pack current
current within ±5% battery
capacity
5 min.
Deviation voltages and temperatures
Table 21 Deviation voltage and temperature boundary limits slave BMS
Boundary condition
Name
Level
Default
Performance
Time
Deviation cell voltage
Set
Difference highest and lowest cell
voltage >= 200 mV;
lowest cell voltage >= 3225;
current within ±5% battery capacity
4-6 min.
Clear
Difference highest and lowest cell
voltage < 160 mV;
lowest cell voltage >= 3225;
current within ±5% battery capacity
4-6 min.
Deviation cell temperature
Set
Difference highest and lowest cell
temperature >= 10 °C
4-6 min.
Clear
Difference highest and lowest cell
temperature < 8 °C
4-6 min.