Battery rack dimension requirements
Figure 10 shows the minimum spacing of the battery modules.
Figure 10 - Battery rack dimension requirements
Cables lengths
Cable lengths need to be taken into account when designing a battery rack. When designing the
battery rack and configuration, cable lengths for different configurations are needed. Batteries can
be placed in parallel, for example in 48 VDC systems, or in series up to 800 VDC.
7.2.2.1
Parallel configuration
To use the battery module in parallel configuration, each battery module is connected with a
separate set of power cables to a junction box.
NOTICE:
When connecting battery modules in parallel to a junction box:
The cable lengths from each battery module need to have exactly the
same length.
Each battery module must be fused separately when paralleld, e.g. in the
junction box.