To provide a connection to a standard ducting system there are two optional parts available as
shown in figure 12.
Figure 12 - Optional exhaust parts
The exhaust parts can be fitted on the battery modules exhaust to provide a flange or a sleeve to
connect to standard 80 mm steel ducting system, as shown in figure 13. The seal in the parts will
make a gas-tight connection that can handle the temperatures during a thermal runaway event.
Figure 13 - Exhaust parts connected
NOTICE:
Water or other liquids may not enter the exhaust ducting. Make sure this is
avoided by design.
CAUTION:
The output of the exhaust ducting must be routed to an area where the released
toxic and flammable gasses cannot harm people or be ignited.