16 – Control CS 320 FU / Rev.A 1.01
Control CS 320 FU / Rev.A 1.01 – 17
EN
ON/OFF key switch
NC contact for interrupting the door function (optional).
This switch is part of the safety circuit.
X6
X6
5.8 / 9
J
J
Jumper (bridge)
The jumper must be connected if the key switch is not
connected.
5.9
5.9 Light grid connection
Light grid connection
It is possible to connect up to 2 light grids to the CS 320 FU
Light grid 1 is connected to the closing edge protective device
input. Light grid 2 is connected to programmable input 2.
Light grid 1
Parameter SKS = MOD4
The connection cable (A) is pluggable.
1
2
3
4
5
6
7
8
9
10
A
BK
BU
WH
BN
X4
GN
GY
11
12
5.9 / 1
Light grid 2
Parameter INPUT 2 = MOD 12
The connection cable (A) is pluggable.
1
2
3
4
5
6
7
8
9
10
A
BK
BU
WH
BN
X4
GN
GY
11
12
5.9 / 2
Legend:
BK Black
GN Green
GY Grey
BU Blue
WH White
BN Brown
R Receiver
T Transmitter
NOTE:
The GridScan/Pro light grids from Cedes are shown on an
exemplary basis in this manual.
The GridScan/Pro light grids correspond to
− Performance Level d, category 2 per EN ISO 13849-1
− Protection level E per EN 12453:2017
Diagrams from other manufacturers on inquiry.
REFERENCE
For a precise description of the function and connection,
refer to the separate documentation for the light grid.