EN
Control CS 320 FU / Rev.A 1.01 – 55
MOD
Description
Remarks
MOD5
Switch BMA 3 (Sect. opening) NO
Control function with an active fire alarm system.
Open:
Normal function.
Closed:
Sect. opening of the door. The intermediate OPEN position (Sect. OPEN) is approached
from both directions, irrespective of the current door position.
BUTTON:
No function.
LB / SKS:
Door stops and moves clear (only in CLOSE direction), after
5 seconds renewed closing.
STOP:
Interruption of the emergency closing for the duration of activation.
MOD6
Switch BMA 1 (emergency closing)
NO
Control function with an active fire alarm system.
Open:
Normal function.
Closed:
Emergency closing of the door.
BUTTON:
No function.
LB / SKS:
Door stops and moves clear, after 5 seconds renewed emergency
closing.
STOP:
Interruption of the emergency closing for the duration of activation.
MOD7
Switch BMA 1 (emergency closing)
NC
Control function with an active fire alarm system.
Closed:
Normal function.
Open:
Emergency closing of the door.
BUTTON:
No function.
LB / SKS:
Door stops and moves clear, after 5 seconds renewed emergency
closing.
STOP:
Interruption of the emergency closing for the duration of activation.
MOD8
Switch BMA 2 (emergency opening)
NO
Control function with an active fire alarm system.
Open:
Normal function.
Closed:
Emergency opening of the door.
BUTTON:
No function.
LB / SKS:
No function.
STOP:
Interruption of the emergency opening for the duration of activation.
No automatic closing after deactivation of the BMA signal.
MOD9
Switch BMA 2 (emergency opening)
NC
Control function with an active fire alarm system.
Closed:
Normal function.
Open:
Emergency opening of the door.
BUTTON:
No function.
LB / SKS:
No function.
STOP:
Interruption of the emergency opening for the duration of activation.
No automatic closing after deactivation of the BMA signal.
MOD10
Button ventilation function NO
Sect. opening of the door. By pressing an additional button at input 1, the intermediate CLOSED position
(Sect. CLOSED) is approached from both directions, independent of the current door position.
MOD11
“Automatic closing” button
1. Actuation:
No automatic closing, open time is stopped.
2. Actuation:
Automatic closing is active again if open time > 0.
3. Actuation:
No automatic closing, open time is stopped.
…
MOD12
Laser scanner (height detection)
Only in conjunction with input 2 (MOD6).
➔
See explanations for input 2