Control CS 320 FU / Rev.A 1.01 – 63
Fault / message
Cause
Rectification
ERROR BRAKE
– Monitoring module BWM1 has identified a
defect at relay 4.
– The circuit board must be replaced.
ERROR INVERTER
Communication fault.
– Communication between frequency converter
and control CS310 interrupted and/or broken
down.
– Bridge (F) missing between DIC and 0V.
– Check communication cable (C) and plug-in connections
to control and frequency converter.
– Use bridge (F) between DIC and 0V (only with frequency
converter type V20).
– Confirm with the STOP button.
ERROR INVERTER 1
Overcurrent.
– Motor rating does not correspond to converter
rating.
– Short-circuit in the motor cable.
– Earth leakage.
– Check motor rating / inverter rating.
– Check motor / motor cable for short-circuit and earth
leakage.
– Adjust the motor parameter settings to the information on
the type plate.
– Check that the the door/gate system runs smoothly.
– Check the spring balance in sectional doors.
– Confirm with the STOP button.
ERROR INVERTER 2
Overvoltage.
– Mains voltage too high.
– Motor is working generator-based due to
ramping down too fast or due to an active load
which is driving the motor.
– Check the voltage supply to the door operator and the
control.
– Confirm with the STOP button.
ERROR INVERTER 3
Undervoltage.
– Mains voltage too low.
– Mains voltage supply failed.
– Check the voltage supply to the door operator and the
control.
– Check that all connections are firmly attached.
– Confirm with the STOP button.
ERROR INVERTER 4
Inverter overtemperature.
– Inverter overloaded.
– Ambient temperature too high.
– Check motor rating / inverter rating.
– Adjust the motor parameter settings to the information on
the type plate.
– Check duty cycle.
– Check that the the door/gate system runs smoothly.
– Check the spring balance in sectional doors.
– Confirm with the STOP button.
ERROR INVERTER 5
Inverter I2T
– Inverter overloaded.
– Motor rating does not correspond to converter
rating.
– Load cycle too high.
– Check motor rating / inverter rating.
– Adjust the motor parameter settings to the information on
the type plate.
– Check load cycle.
ERROR INVERTER 11
Motor overtemperature 12.T
– Motor overloaded.
– Check that the the door/gate system runs smoothly.
– Check the spring balance in sectional doors.
– Confirm with the STOP button.
ERROR INVERTER 51
Internal fault.
– Get in touch with our customer service.
ERROR INVERTER 52
Internal fault.
– Get in touch with our customer service.
ERROR INVERTER 60
Internal fault.
– Get in touch with our customer service.
ERROR INVERTER 72
Internal fault.
– Get in touch with our customer service.
ERROR INVERTER 85
External fault.
– External fault through command input using
terminals.
– Check connection terminals of communication cable (D)
on inverter.
– Confirm with the STOP button.