4.2.5.2 Managers
The FCM9002 supports upto 10 separate SNMP Managers which may be
configured using the managers menu system. Only SNMP polls and get/set
requests from configured managers will be accepted.
The managers menu is as below:
Metrodata FCM9002 "FCM9002 " Alarms: Major
MANAGERS
1 - 192.168.100.45
<menu>
2 - 192.168.100.70
<menu>
Add manager
<menu>
First CAPITAL - select item
<escape> - exit menu
Here there are two managers currently configured which may be selected for
viewing, editing by typing the manager number, in this case 1 which will then
display the parameters for this manager:
Metrodata FCM9002 "FCM9002_Right" Alarms: Major
1 - 192.168.100.45
IP address 192.168.100.45
Access rights Read-Write
receives Traps Yes
snmp Version SNMPv2c
Remove manager
First CAPITAL - select item
<escape> - exit menu
The parameters required for an SNMP manager are the IP address. Note, that
the routing table must be configured where the manager is not on the same
subnet as the FCM9002.
The manager configuration controls the access rights that the manager has,
which may be NONE, READ-ONLY, or READ-WRITE.
The manager may also be set up for traps, if enabled the FCM9002 will generate
traps destined for this manager when alarm events occur.
The FCM9002 supports SNMP V1 or V2c on a per manager basis.