27
C
- ANALOG OPERATING SYSTEM :
(Standard 24 VAC/DC)
Make sure you check the motor type before
making an analog connection to SSM-6
motors. To do so, compare the label
information
on the motor with the
selection table in
Figure 1,
and make sure
the product is correct. Any fault in this
regard with result in damage to the SSM-6
Motor !
For analog connections,
use screened cables
!
Figure 21 :
Analog Electrical Connection in SSM-6 Motors
Analog inputs in SSM-6 Motors are as follows. If no analog input or output values are specified by
the customer in the purchase order, SSM-6 Servo Motors are programmed, at the factory, to input
and output values of 4-20 mA (It is a factor if there is output analog module). Bottom switch
positions in the analog operation system are as in the
Figure 24-25
.
• 0-10V
• 2-10V
• 0-20 mA.
• 4-20 Ma
Bottom switch positions for Analog Inputs/Outputs :
SSM-6 must be deenergized when positioning the bottom switch.
INPUT POSITIONS
OUTPUT POSITIONS
0-10 V
0-10 V
2-10 V
2-10 V
0-20 mA.
0-20 mA.
4-20 mA.
4-20 mA.
Figure 22 :
For Analog Input
Figure 23 :
For Analog Output
bottom switch positions
bottom switch positions