MERAWEX ZUP-230V Скачать руководство пользователя страница 9

User manual   ZUP-230V  

             

Nr dok. 0697.00.95-02.3                                       

8/15 

 

 

Fig.5.

 

Voltage timing for AC-3 output. 

 

If the voltage was present at the AC-3 output, it disappears after a fire alarm occurred for its 

duration, but not shorter than T2+T3 (see the description of the times of the AC-1 output). The 
response to a fire alarm always takes place with a delay of ~2s required for its correct recognition. The 
voltage recovery at the AC-3 output is possible when the mains present and when is no fire alarm. The 
voltage on this output is additionally maintained also after the mains power failure in the absence of a 
fire alarm, so as not to unnecessarily move the devices to the position appropriate for the fire alarm 
only due to the power failure. The voltage maintenance in this state is limited by the maximum battery 
life T1. 

When switching from the mains to the inverter operation, there is a temporary voltage drop on the 

output (about 150ms). 

 

Outputs AC-4A and AC-4B 

 
The AC-4 output is intended for devices that should start operating with some delay after a fire 

alarm, e.g. 

smoke exhaust fan, which can be activated only after passing the shut-off valve to the fully 
open position; 

self-braking, two-way actuator of fire ventilation shutting-off damper, which should close the 
damper only after stopping the fan. 

cascade-operated devices to reduce the inrush current. 

 

 

 

Fig.6.

 

Time waveforms for AC-4 output. 

 

The AC-4 output has the AC-2 output functionality. The only difference is the additional delay in 

switching after the fire alarm is recognized by the T3 time (see the description of the times for the AC-
1 output). 

The response to a fire alarm always takes place with a delay of ~2s required for its correct 

recognition. If the fire alarm occurred with the inverter turned off, it will be restarted with an additional 
delay of about 10s. 

 

 
 

  

OUTPUT  AC-3

 

T2+T3

 

T1

 

~150ms

 

~2s

 

MAINS POWER

 

FIRE ALARM

 

OUTPUT  AC-4A

 

OUTPUT  AC-4B

 

T2

 

~2s

 

T3

 

T2

 

~2s

 

~10s

 

T3

 

MAINS POWER

 

FIRE ALARM

 

Operating from 

BATTERY 

 

Operating from 

MAINS 

 

Operating from 

BATTERY 

 

Содержание ZUP-230V

Страница 1: ...OWER SUPPLY ZUP 230V The document contains USER MANUAL Power supply for fire alarm devices heat and smoke control systems fire protection and fire automation systems ZUP 230V 400 ZUP 230V 700 ZUP 230V...

Страница 2: ...f admittance CNBOP No 3183 2018 14 May 2018 Technical description 2 1 1 Application 2 1 2 Technical data 3 Construction 4 Functioning of outputs 6 Description of 230Vac distribution packet of ZUP powe...

Страница 3: ...while waiting for a fire alarm This allows to extend the supervision time to 72h while maintaining the readiness to operate powered devices with full power depending on the type 400 1500W The power su...

Страница 4: ...bottom ZUP 230V 8 Dimensions and weight A B C D E F G Weight with battery ZUP 230V 400 700 1000 455 406 207 438 310 360 410 42 kg 45Ah ZUP 230V 1500 555 456 207 488 410 410 470 65 kg 75Ah Fig 1 Dimens...

Страница 5: ...A Environmental class EN 12101 10 2007 class 1 Radio disturbances EN 55022 2013 class B EMC immunity EN 50130 4 2012 A1 2015 EMC emission EN 61000 3 2 2007 A1 2010 A2 2010 EN 61000 3 3 2011 Construct...

Страница 6: ...ime it takes to switch from the mains to the battery operation mode Its starting and backup operation takes place from the ZSP121N DR power supply output Then the ZINW 1 connector and the correspondin...

Страница 7: ...tage for some time e g aeration gate drive activated by a separate fire alarm signal but it requires 230V power to operate shunt trips of fire protection circuit breaker it is activated manually with...

Страница 8: ...ins is present The voltage on this output is maintained for a certain period of time T2 T3 see the description of the times of the AC 1 output so that the actuator can change its state The response to...

Страница 9: ...utput about 150ms Outputs AC 4A and AC 4B The AC 4 output is intended for devices that should start operating with some delay after a fire alarm e g smoke exhaust fan which can be activated only after...

Страница 10: ...l contact connector of the PE mains unused ZAS ZSP 230V Additional 230Vac mains output unused PROG UP programming connector do not connect G201 Digital communication connector do not connect WYUSZ Fau...

Страница 11: ...ashing line fault of fire alarm input from the CSP detected T2 T3 T2 and T3 countdown start signalization yellow LED it is possible to finish countdown of these times faster by means of TEST button Co...

Страница 12: ...the HDGs type 1 5mm2 is recommended For devices made in the 2nd class of insulation it is possible to use 2 wire cables without using the connection with the PE bus bar Several loads can be connected...

Страница 13: ...cannot differ by more than 10 for the binary input the short circuit resistance cannot be higher than 1k and the leakage resistance between lines must not be lower than 100k If these values are exceed...

Страница 14: ...th the battery connected and the mains on should result in appearing the voltage on the AC 1 output After power failure the voltage should be maintained for the time T1 Starting the PSU from the batte...

Страница 15: ...s of the power supply Time T1 maximum battery life after power failure from 1min up to 8h Setting sum of individual settings 1 2 5 10 30min and 1 2 5h Example in picture 1 5 10 min 1 2 h 3h and 16min...

Страница 16: ...nt of the waste This marking on the product indicates that the product should not be disposed of with municipal waste at the end of its usage time but must be returned to the collection point for wast...

Страница 17: ...description near the connector Do not obstruct the ventilation Provide at least free space of at least 10cm on the sides of the device allowing the proper ventilation Otherwise the device may be damag...

Страница 18: ...limitation Correct end of bulk charging 2h from moment when charging current drops to 90 Immediately after current drops below 25 of charging current Bulk charging emergency termination battery temper...

Страница 19: ...lectromagnetic compatibility EN 50130 4 A1 Electrical safety Class I acc to EN 60950 1 A1 Mechanical parameters Dimensions body maximum dimension over the TS 35 rail 160 97 46 mm 54 mm 160 53 5 46 12...

Страница 20: ...with two maintenance free batteries which should be placed in its immediate vicinity The end of the temperature sensor of the power supply should be inserted between the two batteries which afterward...

Страница 21: ...diode of internal signalization yellow BAT 21 LED diode of internal signalization green MAINS Notes For each fault signal outputs there are 3 relay contacts available The description of the relay con...

Страница 22: ...he energized state The state of the relay can be tested for example with an ohmmeter applied between the appropriate outputs of its contacts After removing the interruption in the battery circuit the...

Страница 23: ...horized access to the interior of the cabinet Opening the cabinet door after opening the lock causes opening the sensor contacts and generating a fault signal flashing of the FAULT LED of the external...

Страница 24: ...eshold Reaction time 0 immediate reaction x the selected rows describe permanent states of operation preceding the start of the power supply LED signalization inside power supply PCB packet MAINS gree...

Отзывы: