User manual   ZSP121N-DR

             

Nr dok. 0696.00.95-02.0                                       Strona 

2/8 

 

Electrical parameters. 

Power 

 

Mains 

165…230…253V 50Hz 

Power factor 

0.66 

Leakage current in the protective conductor 

0.6mA 

Efficiency in nominal conditions 

87% 

Output 

 

Number of outputs 

Protection of outputs 

fuses 5x20mm 6.3AF

 

Output voltage 

- with battery connected 
- without batteries 

 
21.0…28.8V (depending on battery condition and 
ambient temperature) 
26.4…28.8V (depending on ambient temperature) 

Max. output current 

4.5A (total from both outputs) 

Hiccup type overload protection 

after overloading of up to 10V (at current of 5.5A) 

Ripple voltage 

max. 150mVpp 

Output current Imax. b *1) 

4A 

Output current Imax. a *1) 

- with batteries of 45Ah 
- with batteries of 75Ah 

acc. to EN 54-4 

2.35A 
1.25A 

acc. to EN 12101-10 

0.46A/72h; 

1.13A/30h 

0.78A/72h 

Battery bank control 

 

Output protection 

fuse 5x20mm 8AF

 

Battery charging current limitation 

*2) 

- for batteries of 45Ah 
- for batteries of 75Ah 

 
1.7A  (

CL

 plugs open 

– jumper removed)

 

2.8A  (

CL

 shorted 

– jumper on) 

Bulk charging start 

5 min after exceeding 25% level of charging current 
limitation

 

Correct end of bulk charging 

- 2h from moment when charging current drops to     
90% 
- Immediately after current drops below 25% of 
charging current 

Bulk charging emergency termination 

 

- battery temperature 

has exceeded 40°C 

- temperature sensor fault detected 
- total charging time exceeded 20h when limitation of 
2.8A and 18h at 1.7A 

Floating operation voltage at 25°C 

27.1V (2.26V/cell) 

Bulk charging voltage 

at 25°C 

27.8V (2.32V/cell) 

Temperature compensation of floating 
operation voltage and bulk charging 

-4

8mV/°C (-4.0mV/cell/°C)

 

Overriding battery voltage limits 
- minimum voltage 
- maximum voltage 

 
26.4V (2.2V/cell) 
28.8V (2.4V/cell) 

LVDD at  

21V 

Battery connection 
- recognition of battery connection 
- automatic battery connection 

 
>10V (signalization only) 
>21.6V (1.8V/cell) 

Quiescent current consumption from batteries  
- battery connected 
- battery disconnected 

 
16mA (without external LED signalization 7mA) 
160uA 

Measurement of battery circuit resistance 
- Ri max * 1) 
- measurement repetition period 

only during floating operation  
45

mΩ/45Ah; 

34

mΩ/75Ah     *2) 

10min 

Relay signalization outputs 

 

Output characteristics 
- number of relays 
- maximum loadability of contacts 
- type of contacts available 
- active signalization state 
 

 

30Vdc/1A 
three switchable contacts (NO and NC) 
relay de-energized 

Содержание ZUP-230V

Страница 1: ...OWER SUPPLY ZUP 230V The document contains USER MANUAL Power supply for fire alarm devices heat and smoke control systems fire protection and fire automation systems ZUP 230V 400 ZUP 230V 700 ZUP 230V...

Страница 2: ...f admittance CNBOP No 3183 2018 14 May 2018 Technical description 2 1 1 Application 2 1 2 Technical data 3 Construction 4 Functioning of outputs 6 Description of 230Vac distribution packet of ZUP powe...

Страница 3: ...while waiting for a fire alarm This allows to extend the supervision time to 72h while maintaining the readiness to operate powered devices with full power depending on the type 400 1500W The power su...

Страница 4: ...bottom ZUP 230V 8 Dimensions and weight A B C D E F G Weight with battery ZUP 230V 400 700 1000 455 406 207 438 310 360 410 42 kg 45Ah ZUP 230V 1500 555 456 207 488 410 410 470 65 kg 75Ah Fig 1 Dimens...

Страница 5: ...A Environmental class EN 12101 10 2007 class 1 Radio disturbances EN 55022 2013 class B EMC immunity EN 50130 4 2012 A1 2015 EMC emission EN 61000 3 2 2007 A1 2010 A2 2010 EN 61000 3 3 2011 Construct...

Страница 6: ...ime it takes to switch from the mains to the battery operation mode Its starting and backup operation takes place from the ZSP121N DR power supply output Then the ZINW 1 connector and the correspondin...

Страница 7: ...tage for some time e g aeration gate drive activated by a separate fire alarm signal but it requires 230V power to operate shunt trips of fire protection circuit breaker it is activated manually with...

Страница 8: ...ins is present The voltage on this output is maintained for a certain period of time T2 T3 see the description of the times of the AC 1 output so that the actuator can change its state The response to...

Страница 9: ...utput about 150ms Outputs AC 4A and AC 4B The AC 4 output is intended for devices that should start operating with some delay after a fire alarm e g smoke exhaust fan which can be activated only after...

Страница 10: ...l contact connector of the PE mains unused ZAS ZSP 230V Additional 230Vac mains output unused PROG UP programming connector do not connect G201 Digital communication connector do not connect WYUSZ Fau...

Страница 11: ...ashing line fault of fire alarm input from the CSP detected T2 T3 T2 and T3 countdown start signalization yellow LED it is possible to finish countdown of these times faster by means of TEST button Co...

Страница 12: ...the HDGs type 1 5mm2 is recommended For devices made in the 2nd class of insulation it is possible to use 2 wire cables without using the connection with the PE bus bar Several loads can be connected...

Страница 13: ...cannot differ by more than 10 for the binary input the short circuit resistance cannot be higher than 1k and the leakage resistance between lines must not be lower than 100k If these values are exceed...

Страница 14: ...th the battery connected and the mains on should result in appearing the voltage on the AC 1 output After power failure the voltage should be maintained for the time T1 Starting the PSU from the batte...

Страница 15: ...s of the power supply Time T1 maximum battery life after power failure from 1min up to 8h Setting sum of individual settings 1 2 5 10 30min and 1 2 5h Example in picture 1 5 10 min 1 2 h 3h and 16min...

Страница 16: ...nt of the waste This marking on the product indicates that the product should not be disposed of with municipal waste at the end of its usage time but must be returned to the collection point for wast...

Страница 17: ...description near the connector Do not obstruct the ventilation Provide at least free space of at least 10cm on the sides of the device allowing the proper ventilation Otherwise the device may be damag...

Страница 18: ...limitation Correct end of bulk charging 2h from moment when charging current drops to 90 Immediately after current drops below 25 of charging current Bulk charging emergency termination battery temper...

Страница 19: ...lectromagnetic compatibility EN 50130 4 A1 Electrical safety Class I acc to EN 60950 1 A1 Mechanical parameters Dimensions body maximum dimension over the TS 35 rail 160 97 46 mm 54 mm 160 53 5 46 12...

Страница 20: ...with two maintenance free batteries which should be placed in its immediate vicinity The end of the temperature sensor of the power supply should be inserted between the two batteries which afterward...

Страница 21: ...diode of internal signalization yellow BAT 21 LED diode of internal signalization green MAINS Notes For each fault signal outputs there are 3 relay contacts available The description of the relay con...

Страница 22: ...he energized state The state of the relay can be tested for example with an ohmmeter applied between the appropriate outputs of its contacts After removing the interruption in the battery circuit the...

Страница 23: ...horized access to the interior of the cabinet Opening the cabinet door after opening the lock causes opening the sensor contacts and generating a fault signal flashing of the FAULT LED of the external...

Страница 24: ...eshold Reaction time 0 immediate reaction x the selected rows describe permanent states of operation preceding the start of the power supply LED signalization inside power supply PCB packet MAINS gree...

Отзывы: