MERAWEX ZUP-230V Скачать руководство пользователя страница 22

User manual   ZSP121N-DR

             

Nr dok. 0696.00.95-02.0                                       Strona 

6/8 

First start 

 
If all connections have been made correctly after connecting the power supply to the mains, the 

green 

MAINS

 signalization diode on the power supply packet and the 

MAINS

 diode of the eternal 

indication should be on.  

 
Two checks must be performed when starting the device. 

 

Checking capacity of maintaining output voltage. 
 

Disconnect the mains with the switch mounted on the power supply casing. The power supply 

should go into the battery operation mode, maintaining the voltage on its both outputs. You can use any 
voltage tester for the purpose, e.g. a voltmeter or a light bulb. 
 

Note. 

Connecting the battery to operate inside the power supply occurs only when the battery voltage is 

higher than 21.6V.

 

 

After disconnecting the mains, the green 

MAINS

 LED on the power supply packet should go out and 

its counterpart of external signalization should be flashing. At the same time, the 

MAINS FLT

 relay 

should go into the standby mode (the position of contacts in accordance with the drawing near the 
connector). 

The transition into the battery operation is also signaled by the 

FAULT

 LED of the external 

signalization and the 

GEN FLT

 relay should go into the standby mode with delay of 5s. 

 
Battery circuit test 

 

Break the battery circuit by disconnecting one of the cables when the power supply is in the mains 

operation mode. This state will be detected by the power supply at the nearest test within 90s and 
signaled by flashing of the 

BAT

 diode. 

In this state, the external 

LED FAULT

 signalization should be activated and the 

GEN FLT

 relay 

should go into the standby mode (the position of contacts in accordance with the drawing near the 
connector). However, the 

MAINS FLT

 relay should remain in the energized state. The state of the relay 

can be tested, for example, with an ohmmeter applied between the appropriate outputs of its contacts. 

After removing the interruption in the battery circuit, the generated fault signalization will be 

removed automatically. This can happen immediately when the battery status starts the battery 
charging or only after 90 seconds, at the next, correctly performed test.

 

 

Notes on operation and servicing

 

 

Output voltage values as well as signalization thresholds are pre-set. The power supplies after their 

installation require supervision related only to faults that may occur during the operation of the device. 

The battery bank is connected by the power supply when only the mains is on and if the battery 

voltage is higher than 21.6V. If the battery is faulty (with less than 10V), its installation will not be 
recognized by the power supply in any way. For average voltages, the warning signalization is activated 
in the form of short flashes of the external 

FAULT

 LED signalization, but the battery itself will not be 

connected. 
 
     In the battery mode, when the mains is out, after discharging the battery down to 21V, the batteries 
are disconnected, so their complete discharge does not influence the battery lifetime. 
 
Note 1. 
Disconnecting the batteries from the load after their discharge protects the batteries against 
deterioration, but only under the condition that the power supply failure will not last too long (e.g. several 
days). Lack of recharging the batteries for longer time can lead to the battery voltage self-limitation, 
which will prevent the batteries from automatic connection after the mains returns.   
 
Note 2. 
It should be noted that the power supply itself receives a certain current for its own needs, which in the 
absence of mains power, can lead to discharging the batteries even in the case when the load has been 
completely disconnected. Such the situation can take place, for example, when installing power 

Содержание ZUP-230V

Страница 1: ...OWER SUPPLY ZUP 230V The document contains USER MANUAL Power supply for fire alarm devices heat and smoke control systems fire protection and fire automation systems ZUP 230V 400 ZUP 230V 700 ZUP 230V...

Страница 2: ...f admittance CNBOP No 3183 2018 14 May 2018 Technical description 2 1 1 Application 2 1 2 Technical data 3 Construction 4 Functioning of outputs 6 Description of 230Vac distribution packet of ZUP powe...

Страница 3: ...while waiting for a fire alarm This allows to extend the supervision time to 72h while maintaining the readiness to operate powered devices with full power depending on the type 400 1500W The power su...

Страница 4: ...bottom ZUP 230V 8 Dimensions and weight A B C D E F G Weight with battery ZUP 230V 400 700 1000 455 406 207 438 310 360 410 42 kg 45Ah ZUP 230V 1500 555 456 207 488 410 410 470 65 kg 75Ah Fig 1 Dimens...

Страница 5: ...A Environmental class EN 12101 10 2007 class 1 Radio disturbances EN 55022 2013 class B EMC immunity EN 50130 4 2012 A1 2015 EMC emission EN 61000 3 2 2007 A1 2010 A2 2010 EN 61000 3 3 2011 Construct...

Страница 6: ...ime it takes to switch from the mains to the battery operation mode Its starting and backup operation takes place from the ZSP121N DR power supply output Then the ZINW 1 connector and the correspondin...

Страница 7: ...tage for some time e g aeration gate drive activated by a separate fire alarm signal but it requires 230V power to operate shunt trips of fire protection circuit breaker it is activated manually with...

Страница 8: ...ins is present The voltage on this output is maintained for a certain period of time T2 T3 see the description of the times of the AC 1 output so that the actuator can change its state The response to...

Страница 9: ...utput about 150ms Outputs AC 4A and AC 4B The AC 4 output is intended for devices that should start operating with some delay after a fire alarm e g smoke exhaust fan which can be activated only after...

Страница 10: ...l contact connector of the PE mains unused ZAS ZSP 230V Additional 230Vac mains output unused PROG UP programming connector do not connect G201 Digital communication connector do not connect WYUSZ Fau...

Страница 11: ...ashing line fault of fire alarm input from the CSP detected T2 T3 T2 and T3 countdown start signalization yellow LED it is possible to finish countdown of these times faster by means of TEST button Co...

Страница 12: ...the HDGs type 1 5mm2 is recommended For devices made in the 2nd class of insulation it is possible to use 2 wire cables without using the connection with the PE bus bar Several loads can be connected...

Страница 13: ...cannot differ by more than 10 for the binary input the short circuit resistance cannot be higher than 1k and the leakage resistance between lines must not be lower than 100k If these values are exceed...

Страница 14: ...th the battery connected and the mains on should result in appearing the voltage on the AC 1 output After power failure the voltage should be maintained for the time T1 Starting the PSU from the batte...

Страница 15: ...s of the power supply Time T1 maximum battery life after power failure from 1min up to 8h Setting sum of individual settings 1 2 5 10 30min and 1 2 5h Example in picture 1 5 10 min 1 2 h 3h and 16min...

Страница 16: ...nt of the waste This marking on the product indicates that the product should not be disposed of with municipal waste at the end of its usage time but must be returned to the collection point for wast...

Страница 17: ...description near the connector Do not obstruct the ventilation Provide at least free space of at least 10cm on the sides of the device allowing the proper ventilation Otherwise the device may be damag...

Страница 18: ...limitation Correct end of bulk charging 2h from moment when charging current drops to 90 Immediately after current drops below 25 of charging current Bulk charging emergency termination battery temper...

Страница 19: ...lectromagnetic compatibility EN 50130 4 A1 Electrical safety Class I acc to EN 60950 1 A1 Mechanical parameters Dimensions body maximum dimension over the TS 35 rail 160 97 46 mm 54 mm 160 53 5 46 12...

Страница 20: ...with two maintenance free batteries which should be placed in its immediate vicinity The end of the temperature sensor of the power supply should be inserted between the two batteries which afterward...

Страница 21: ...diode of internal signalization yellow BAT 21 LED diode of internal signalization green MAINS Notes For each fault signal outputs there are 3 relay contacts available The description of the relay con...

Страница 22: ...he energized state The state of the relay can be tested for example with an ohmmeter applied between the appropriate outputs of its contacts After removing the interruption in the battery circuit the...

Страница 23: ...horized access to the interior of the cabinet Opening the cabinet door after opening the lock causes opening the sensor contacts and generating a fault signal flashing of the FAULT LED of the external...

Страница 24: ...eshold Reaction time 0 immediate reaction x the selected rows describe permanent states of operation preceding the start of the power supply LED signalization inside power supply PCB packet MAINS gree...

Отзывы: