MERAWEX ZUP-230V Скачать руководство пользователя страница 12

User manual   ZUP-230V  

             

Nr dok. 0697.00.95-02.3                                       

11/15 

 

5.2.  Connecting mains 

 

The mains power cable with a minimum cross-

section of 3×1.5 mm2, after passing through one of 

the glands in the casing of the power supply, should be connected to single-track connectors, as 
shown in the Fig.2. 
 

Note.

 

The mains connection must be made as a permanent installation with the continuity of the neutral 

line (N). The installation switch described below must be in the active line (L). 

 
The power supply is not equipped with its own mains switch, therefore it is required to use a special 

installation switch outside the power supply. The switch should also be used as an overload and short-
circuit protection device and allow to power the devices of high inrush current. We recommend using 
the S301 C16A installation switch. This switch should be clearly marked as being used in the fire 
system and cannot be used simultaneously in other circuits. 

 

Warning. 

Switching on the mains with a switch located outside the power supply can only be performed with 

the fully assembled internal cabling of the power supply unit, including the connected and correctly 
installed inverter. It is unacceptable to leave the 230Vac power plug disconnected from the inverter 
output. 

5.3.  Connection of external AC output circuits 

 

The external connections cables should be run through the selected holes in the cabinet's body 

(after removing the jumpers) and fastened by twisting the appropriate glands. The cables to be 
connected to the AC-1, AC-2, AC-3 and AC-4 outputs, after fixing them in the glands, should be led in 
a large arc in the inverter plane before they are fixed by cable holders and connected to appropriate 
terminals of the ZUP power supply . The external cable insulation should be removed directly behind 
the cable holder. To make the connections of 230Vac power in the fire protection systems, 3-wire 
cable of the HDGs type 1.5mm2 is recommended. For devices made in the 2nd class of insulation, it is 
possible to use 2-wire cables, without using the connection with the PE bus bar. 

 
Several loads can be connected to the power supply at the same time. The sum of their power 

cannot, however, exceed the maximum power indicated for a given execution device. Attention should 
be paid to the nature of the load provided by some loads. For example, induction motors can take 
significant current when starting, which can lead to a blown fuse placed on a given output or prevent 
proper start of the inverter. In this case, it is possible to use a soft starter system (so called soft-
starter), for example, the ZUP-MS type of the MERAWEX. However, a user is asked to consult the 
manufacturer, due to different nature of loads, which may require setting individual device operation 
parameters. 
 

5.4.  Connection of additional outputs 

These connections concern the outputs of the ZSP121N-DR power supply shown in Fig.2. It should 

be noted that all signal outputs and inputs are referenced to the negative output terminal of the power 
supply. A detailed description of the outputs of this power supply is included in a separate User 
Manual. 

From the output 

OUT1

 of the ZSP121N-DR power supply, only current of the values described in 

the table 

Basic operating parameters of power supplies

 can be taken (point 1.2 Technical data). 

5.5.  Connection of battery bank 

 

The battery bank, placed with its terminals from the side of the casing door, should be connected 

with two cables that are already led out of the power supply, paying particular attention to the polarity: 
red cable to the positive pole of one battery, blue to the negative of the second one. Finally, connect 
the both batteries with each other, by means of the cable (connector) provided by the manufacturer. 
Incorrect connection can lead to destruction of the power supply. 

The battery should be connected with the battery disconnector switched off and its fuse removed. 

Although each of the component devices (the ZSP121N DR power supply, ZUP and inverter) has its 

Содержание ZUP-230V

Страница 1: ...OWER SUPPLY ZUP 230V The document contains USER MANUAL Power supply for fire alarm devices heat and smoke control systems fire protection and fire automation systems ZUP 230V 400 ZUP 230V 700 ZUP 230V...

Страница 2: ...f admittance CNBOP No 3183 2018 14 May 2018 Technical description 2 1 1 Application 2 1 2 Technical data 3 Construction 4 Functioning of outputs 6 Description of 230Vac distribution packet of ZUP powe...

Страница 3: ...while waiting for a fire alarm This allows to extend the supervision time to 72h while maintaining the readiness to operate powered devices with full power depending on the type 400 1500W The power su...

Страница 4: ...bottom ZUP 230V 8 Dimensions and weight A B C D E F G Weight with battery ZUP 230V 400 700 1000 455 406 207 438 310 360 410 42 kg 45Ah ZUP 230V 1500 555 456 207 488 410 410 470 65 kg 75Ah Fig 1 Dimens...

Страница 5: ...A Environmental class EN 12101 10 2007 class 1 Radio disturbances EN 55022 2013 class B EMC immunity EN 50130 4 2012 A1 2015 EMC emission EN 61000 3 2 2007 A1 2010 A2 2010 EN 61000 3 3 2011 Construct...

Страница 6: ...ime it takes to switch from the mains to the battery operation mode Its starting and backup operation takes place from the ZSP121N DR power supply output Then the ZINW 1 connector and the correspondin...

Страница 7: ...tage for some time e g aeration gate drive activated by a separate fire alarm signal but it requires 230V power to operate shunt trips of fire protection circuit breaker it is activated manually with...

Страница 8: ...ins is present The voltage on this output is maintained for a certain period of time T2 T3 see the description of the times of the AC 1 output so that the actuator can change its state The response to...

Страница 9: ...utput about 150ms Outputs AC 4A and AC 4B The AC 4 output is intended for devices that should start operating with some delay after a fire alarm e g smoke exhaust fan which can be activated only after...

Страница 10: ...l contact connector of the PE mains unused ZAS ZSP 230V Additional 230Vac mains output unused PROG UP programming connector do not connect G201 Digital communication connector do not connect WYUSZ Fau...

Страница 11: ...ashing line fault of fire alarm input from the CSP detected T2 T3 T2 and T3 countdown start signalization yellow LED it is possible to finish countdown of these times faster by means of TEST button Co...

Страница 12: ...the HDGs type 1 5mm2 is recommended For devices made in the 2nd class of insulation it is possible to use 2 wire cables without using the connection with the PE bus bar Several loads can be connected...

Страница 13: ...cannot differ by more than 10 for the binary input the short circuit resistance cannot be higher than 1k and the leakage resistance between lines must not be lower than 100k If these values are exceed...

Страница 14: ...th the battery connected and the mains on should result in appearing the voltage on the AC 1 output After power failure the voltage should be maintained for the time T1 Starting the PSU from the batte...

Страница 15: ...s of the power supply Time T1 maximum battery life after power failure from 1min up to 8h Setting sum of individual settings 1 2 5 10 30min and 1 2 5h Example in picture 1 5 10 min 1 2 h 3h and 16min...

Страница 16: ...nt of the waste This marking on the product indicates that the product should not be disposed of with municipal waste at the end of its usage time but must be returned to the collection point for wast...

Страница 17: ...description near the connector Do not obstruct the ventilation Provide at least free space of at least 10cm on the sides of the device allowing the proper ventilation Otherwise the device may be damag...

Страница 18: ...limitation Correct end of bulk charging 2h from moment when charging current drops to 90 Immediately after current drops below 25 of charging current Bulk charging emergency termination battery temper...

Страница 19: ...lectromagnetic compatibility EN 50130 4 A1 Electrical safety Class I acc to EN 60950 1 A1 Mechanical parameters Dimensions body maximum dimension over the TS 35 rail 160 97 46 mm 54 mm 160 53 5 46 12...

Страница 20: ...with two maintenance free batteries which should be placed in its immediate vicinity The end of the temperature sensor of the power supply should be inserted between the two batteries which afterward...

Страница 21: ...diode of internal signalization yellow BAT 21 LED diode of internal signalization green MAINS Notes For each fault signal outputs there are 3 relay contacts available The description of the relay con...

Страница 22: ...he energized state The state of the relay can be tested for example with an ohmmeter applied between the appropriate outputs of its contacts After removing the interruption in the battery circuit the...

Страница 23: ...horized access to the interior of the cabinet Opening the cabinet door after opening the lock causes opening the sensor contacts and generating a fault signal flashing of the FAULT LED of the external...

Страница 24: ...eshold Reaction time 0 immediate reaction x the selected rows describe permanent states of operation preceding the start of the power supply LED signalization inside power supply PCB packet MAINS gree...

Отзывы: