User manual ZUP-230V
Nr dok. 0697.00.95-02.3
3/15
1.2. Technical data.
Basic operating parameters of power supplies
.
EN 54-4
Max. battery
capacity
Imax_a
Imax_b
230Vac
24Vdc
230Vac
24Vdc
ZUP-230V-400
45Ah
400 W
2.0 A
400 W
3.5 A
ZUP-230V-700
45Ah
700 W
1.9 A
700 W
3.3 A
ZUP-230V-1000
45Ah
1000 W
1.7 A
1000 W
3.2 A
ZUP-230V-1500
75Ah
1500 W
0.4 A
1500 W
3.0 A
EN 12101-10
Max. battery
capacity
Imax_a
Imax_b
230Vac
24Vdc
230Vac
24Vdc
ZUP-230V-400
45Ah
0 W
0.33 A
400 W
3.5 A
ZUP-230V-700
45Ah
0 W
0.26 A
700 W
3.3 A
ZUP-230V-1000
45Ah
0 W
0.15 A
1000 W
3.2 A
ZUP-230V-1500
75Ah
0 W
0.41 A
1500 W
3.0 A
Holes in the
cabinet's bottom
ZUP-230V
8
Dimensions and weight
A
B
C
D
E
F
G
Weight with
battery
ZUP-230V-400 -700 -1000
455
406
207
438
310
360
410
42 kg 45Ah
ZUP-230V-1500
555
456
207
488
410
410
470
65 kg 75Ah
Fig.1.
Dimensions and placement of mounting holes of ZUP-230V power supplies.
Basic electrical and environmental parameters.
Power
Mains voltage
230V - 25% +10% 50Hz
Outputs 230Vac
*1)
Output voltage 230Vac
- when mains present *2)
- when mains absent *2)
equals to mains voltage
230V ±3% 50Hz *3)
Fuses on each output
5x20mm 6.3AF
Output 24Vdc
Rated voltage of output 24Vdc *4)
27.1V
Range of voltage changes 24Vdc *5)
21…28.8V
Battery bank
Maximum battery charging current
- battery of 45Ah
- battery of 47Ah
1.7A
2.8A
Quiescent current consumption from battery
- when inverter is operating
- when inverter is off
0.78A/400W, 0.93A/700W,
1.08A/1000W, 1.33A/1500W
26mA