User manual ZUP-230V
Nr dok. 0697.00.95-02.3
13/15
•
in the initial state, the mains should be disconnected (with the installation switch outside
the power supply) as well as the battery bank (W-BAT switch);
•
each activation of the power supply causes the LEDs to switch on for a moment: INW,
ALP, T2+T3;
•
LED OPERATION is on continuously during operation of the power supply;
•
signalization states have been indicated in the tables below.
Checking 230Vac voltage backup capacity
LED diodes on
box door
LED diodes on 230Vac voltage distribution
packet
Output
MAINS
FAULT
OPERATION
ZINW-1
ZINW-2
INW
AC-1
W-BAT battery switch switched
on (
no reaction required
)
–
–
–
–
–
–
–
W-BAT battery switch switched
off
–
–
–
–
–
–
–
Mains switched on
+
+
+
–
–
+/
–
+
W-BAT battery switch switched
on
+
–
+
+
–
+
+
Mains switched off
+/
–
+
+
+
+
+
+
after time T1
+/
–
+
+
–
–
–
–
Switching on the battery switch (without mains) should not cause a permanent reaction of the
power supply. The correct starting (with the battery connected and the mains on) should result in
appearing the voltage on the AC-1 output. After power failure, the voltage should be maintained for the
time T1.
Starting the PSU from the battery, without mains power ("cold start")
LED diodes on
box door
LED diodes on 230Vac voltage
distribution packet
Output
MAINS
FAULT
PRACA
ZINW-1
ZINW-2
INW
AC-1
W-BAT battery switch
switched on
–
–
–
–
–
–
–
ZST button press
–
–
+
+
+
–
–
after a dozen or so
seconds
+/
–
+
+
–
–
–
–
The ZST button allows you to start the power supply from the battery, without the power supply.
After such the start, the power supply switches into the state corresponding to the end of the T1
countdown in which the power supply during the battery operation waits for a fire alarm signal.
5.7.2. Checking basic functions.
Initial status: power supply switched on, mains on, battery connected.
Initial settings for the CSP fire alarm input:
- CSP PARAM switch:
ON
- AL CSP jumper:
L
Checking operation of CSP fire alarm input.
LED diodes on 230Vac voltage
distribution packet
Output
ALP
ZINW-1
ZINW-2
INW
AC-2A
CSP input not connected
+/
–
+
–
+
+
Connecting 10k
Ω resistor to CSP input
–
+
–
+
+