User manual ZSP121N-DR
Nr dok. 0696.00.95-02.0 Strona
1/8
MERAWEX Sp. z o.o.
44-122 Gliwice
ul. Toruńska 8
Poland
tel. +48 32 23 99 400
fax +48 32 23 99 409
e-mail:
http://www.merawex.com.pl
USER MANUAL
Power supply for fire alarm devices, heat and smoke control systems, fire
protection devices and fire automation
ZSP121N-DR
designed to operate with the power supply ZUP-230V
27 March 2018
Warnings
Read all the tips and recommendations below.
Failure to observe them can cause damage to the
device, electric shock, fire or serious injury.
▪
It is forbidden to transport the device with mounted and connected batteries.
It may result
in serious internal damage and the loss of safety of use.
▪
Installation and connections may be carried out only when the batteries are removed.
▪
When connecting batteries, pay special attention to the polarity compatibility with the
description near the connector.
▪
Do not obstruct the ventilation.
Provide at least free space of at least 10cm on the sides of
the device allowing the proper ventilation. Otherwise, the device may be damaged or battery
bank can be prematurely used out.
▪
Mount the device in a place where it will not be exposed to direct sunlight..
▪
The device must be powered from the mains with a protective earth terminal.
▪
Before connecting the device, check the quality of all connections made
.
▪
The device may affect the operation of sensitive radio and television equipment located
nearby.
▪
The device may only be serviced by the manufacturer's service department or
specialized companies authorized by the manufacturer.
Technical description
The power supplies have been designed for uninterruptible powering of 24V fire protection devices
and meet the requirements of the EN 54-4 and EN 12101-10 standards. The source of backup power
are two, 12V lead-acid batteries of the VRLA type. The power supplies are designed for mounting on
the TS-35 rail, inside cabinets or inside the other IP42 devices.