User manual ZSP121N-DR
Nr dok. 0696.00.95-02.0 Strona
3/8
Binary inputs of external indications
External signal input protection
3.3V/0.7mA, protection
±30V/50mA
Input for connecting tamper switch (tamper)
3.3V/0.7mA
*1) Markings acc. to EN 54-4 + A1 + A2
*2) Possibility of switching by a user. The limitation of the charging current and the threshold of the maximum
resistance of the battery circuit are switched simultaneously.
Operating conditions
Ambient temperature during operation
-
25…+55°C
Storage temperature range
-
25…+85°C
Relative humidity (non-condensing)
30…80%
Direct sun exposure
unacceptable
Surges during operation
unacceptable
Compliance with standards
Basic requirements, functionality
EN 54-4 + A1 + A2, EN 12101-10, ISO 7240-4
Electromagnetic compatibility
EN 50130-4 + A1
Electrical safety
Class I acc. to EN 60950-1 + A1
Mechanical parameters
Dimensions
- body
- maximum dimension over the TS-35 rail
160 × 97 × 46 mm
54 mm
160
53.5
46
12
9
6.
8
5
.2
Power supply assembly:
- temperature sensor (attached permanently or fitted with a plug);
- jumper on the
INT FLT
signalization input connector;
- of the maximum
CL
charging current selection jumper
Optional equipment:
- module of the 6 additional outputs of the ZSP100-OUT6 type
- tamper with the cables
Installation and connection.
The power supply has been designed for mounting on a TS-35 rail and for use with battery banks.
Releasing the latch on the rail is possible by pressing the lever over the power supply with your fingers
or by pulling it down using a screwdriver inserted into a rectangular hole under the power supply.
Removing the power supply is possible by its slight deviation from the rail towards yourself and