User manual ZUP-230V
Nr dok. 0697.00.95-02.3
2/15
Warnings
▪
Before using the device, carefully read this User Manual.
▪
Do not touch the internal components of the operating device - risk of electric shock or
burns.
▪
Protect the device against any objects or liquids entering it - risk of electric shock and
damage to the device.
▪
Do not obscure the ventilation openings - it can damage the device.
▪
Provide at least free space of at least 10cm on the sides of the device allowing proper
ventilation.
▪
It is forbidden to transport the device with mounted and connected batteries.
▪
The device must be powered from the mains with a protective earth terminal.
▪
The device may affect the operation of sensitive radio and television equipment located
nearby
Technical description.
1.1. Application.
The ZUP-230V battery backup power supply provides the 230V uninterruptible voltage from the
mains or after its failure, from the DC/AC 230Vac inverter powered from the internal 24V battery bank.
During power failure, the total power is taken from the battery, its presence and efficiency is an
essential element of the
power supply’s operation.
The power supply is not an UPS. Most fire protection devices supplied with 230V voltage during
supervision stay in standby mode - no power is consumed. The organization of the power
supply’s
work takes into account this fact by setting specific time periods of the inverter's activity, while it takes
energy from the battery. Apart from those time periods the battery is relieved while waiting for a fire
alarm. This allows to extend the supervision time to 72h while maintaining the readiness to operate
powered devices with full power (depending on the type 400 ÷ 1500W).
The power supply enables 230V voltage distribution among 4 various types of receivers requiring
taking, switching or disconnection of power at a given time, depending on a function being performed,
after receiving a signal from outside (e.g. fire alarm). Response times for individual types of outputs
can be set by a user in a wide range by using slide switches. The main application of the ZUP-230V
power supplies includes:
•
aeration gates;
•
shunt trips of fire protection circuit breakers;
•
self-locking, two-way actuators of shutting off dampers of fire ventilation;
•
drives of the fire zone separating gates;
•
spring actuators of fire protection shutting off dampers;
•
blinds of ceiling smoke tanks;
•
smoke exhaust fans running after a shutting off damper goes to the opening position;
•
self-locking, two-way actuators of fire protection shutting off dampers, closed when a fan
stops;
•
devices started in a cascade sequence to reduce the inrush current.
In addition, the 24Vdc uninterruptible voltage of 100W is available to supply other fire protection
devices.
The power supply meets the requirements of the EN 54-4: 2001 + A1: 2004 + A2: 2007 and EN
12101-10: 2007 and the Ordinance of the Ministry of Interior and Administration of the 20 June 2007,
the Book of Acts No. 143 item 1002, with an amendment No. 85 item 553 of 27/04/2010.
In addition, the power supply meets the requirements of the Regulation of the European
Parliament and the Council of Europe (EU) No. 305/2011 of the 9 March 2011. (CPR - Construction
Product Regulation).