Description of ZSP121N-DR power supply elements 

Item 

Description 

Marking 

Recommended type and cross-

section of wire 

1. 

Connector of 230V 50Hz mains 

L, N, PE 

3-wire cable of HDGs type 0.75 ... 
1.5mm

2

 

2. 

Additional protective terminal 

PE 

 

3. 

Mains switch 

 

 

4. 

Mains fuse 

 

 

5. 

Temperature sensor 

TMP 

If it is connected permanently 

6. 

Load connector 1 

OUT 1 

2-wire cable of HDGs type 1.5 or 
2.5mm

2

 

7. 

Load connector 2 

OUT 2 

8. 

Battery connector 

BAT 

 

9. 

Output fuse 1 

 

 

10. 

Output fuse 2 

 

 

11. 

Battery fuse 

 

12. 

General fault signal output 

GEN FLT 

2-wire cable of YnTKSY type 
1x2x0.8mm

2

 

13. 

Mains fault signal output 

MAINS FLT 

14. 

External fault signalization input 

EXT FLT 

15. 

Connector for connecting LED signalization diodes 

LED 

 

16. 

Tamper connector 

INT FLT 

 

17. 

Signaling input from the additional output packet 

EFL 

 

18. 

Temperature sensor connector 

TEMP 

If it is not connected permanently 

19. 

Charging current limitation level switch 

CL 

 

20. 

LED diode of internal signalization 

– yellow 

BAT 

 

21. 

LED diode of internal signalization - green 

MAINS 

 

 

Notes 

 

For each fault signal outputs, there are 3 relay contacts available. The description of the relay 
connector indicates the contact position in the event of power failure (de-energized relay). 

 

The external fault signal input is connected by its terminal (-) to the negative battery terminal (

BAT -

). 

Generation of the fault signalization requires 0V (short-circuit). In this state, the current of 
approximately 0.25mA flows between the terminals (

+

) and (

-

) of the signalization input. 

 

If tamper or another device is intended to be connected to the power supply, the sensor harness 
plug must be inserted instead of the pre-installed 

INT FLT

 jumper. 

 

The only elements that can be replaced by the user are the fuses described in the table below. It is 
permissible to replace the fuses only while maintaining their value and speed. 

 

Position 

in table 

Fuse description 

Value 

4. 

Mains circuit (delayed T)  

1.6 AT 

9. 10. 

Output circuits (fast F) 

6.3 AF 

11. 

Battery circuit (fast F) 

8.0 AF 

 

  The following figure shows the way (polarity) of connecting the external LED signalization system. 

 

LED

2

3

1

4

G

Y

FAULT

MAINS

 

 
 
 
 
 

 
 

Содержание ZUP-230V

Страница 1: ...OWER SUPPLY ZUP 230V The document contains USER MANUAL Power supply for fire alarm devices heat and smoke control systems fire protection and fire automation systems ZUP 230V 400 ZUP 230V 700 ZUP 230V...

Страница 2: ...f admittance CNBOP No 3183 2018 14 May 2018 Technical description 2 1 1 Application 2 1 2 Technical data 3 Construction 4 Functioning of outputs 6 Description of 230Vac distribution packet of ZUP powe...

Страница 3: ...while waiting for a fire alarm This allows to extend the supervision time to 72h while maintaining the readiness to operate powered devices with full power depending on the type 400 1500W The power su...

Страница 4: ...bottom ZUP 230V 8 Dimensions and weight A B C D E F G Weight with battery ZUP 230V 400 700 1000 455 406 207 438 310 360 410 42 kg 45Ah ZUP 230V 1500 555 456 207 488 410 410 470 65 kg 75Ah Fig 1 Dimens...

Страница 5: ...A Environmental class EN 12101 10 2007 class 1 Radio disturbances EN 55022 2013 class B EMC immunity EN 50130 4 2012 A1 2015 EMC emission EN 61000 3 2 2007 A1 2010 A2 2010 EN 61000 3 3 2011 Construct...

Страница 6: ...ime it takes to switch from the mains to the battery operation mode Its starting and backup operation takes place from the ZSP121N DR power supply output Then the ZINW 1 connector and the correspondin...

Страница 7: ...tage for some time e g aeration gate drive activated by a separate fire alarm signal but it requires 230V power to operate shunt trips of fire protection circuit breaker it is activated manually with...

Страница 8: ...ins is present The voltage on this output is maintained for a certain period of time T2 T3 see the description of the times of the AC 1 output so that the actuator can change its state The response to...

Страница 9: ...utput about 150ms Outputs AC 4A and AC 4B The AC 4 output is intended for devices that should start operating with some delay after a fire alarm e g smoke exhaust fan which can be activated only after...

Страница 10: ...l contact connector of the PE mains unused ZAS ZSP 230V Additional 230Vac mains output unused PROG UP programming connector do not connect G201 Digital communication connector do not connect WYUSZ Fau...

Страница 11: ...ashing line fault of fire alarm input from the CSP detected T2 T3 T2 and T3 countdown start signalization yellow LED it is possible to finish countdown of these times faster by means of TEST button Co...

Страница 12: ...the HDGs type 1 5mm2 is recommended For devices made in the 2nd class of insulation it is possible to use 2 wire cables without using the connection with the PE bus bar Several loads can be connected...

Страница 13: ...cannot differ by more than 10 for the binary input the short circuit resistance cannot be higher than 1k and the leakage resistance between lines must not be lower than 100k If these values are exceed...

Страница 14: ...th the battery connected and the mains on should result in appearing the voltage on the AC 1 output After power failure the voltage should be maintained for the time T1 Starting the PSU from the batte...

Страница 15: ...s of the power supply Time T1 maximum battery life after power failure from 1min up to 8h Setting sum of individual settings 1 2 5 10 30min and 1 2 5h Example in picture 1 5 10 min 1 2 h 3h and 16min...

Страница 16: ...nt of the waste This marking on the product indicates that the product should not be disposed of with municipal waste at the end of its usage time but must be returned to the collection point for wast...

Страница 17: ...description near the connector Do not obstruct the ventilation Provide at least free space of at least 10cm on the sides of the device allowing the proper ventilation Otherwise the device may be damag...

Страница 18: ...limitation Correct end of bulk charging 2h from moment when charging current drops to 90 Immediately after current drops below 25 of charging current Bulk charging emergency termination battery temper...

Страница 19: ...lectromagnetic compatibility EN 50130 4 A1 Electrical safety Class I acc to EN 60950 1 A1 Mechanical parameters Dimensions body maximum dimension over the TS 35 rail 160 97 46 mm 54 mm 160 53 5 46 12...

Страница 20: ...with two maintenance free batteries which should be placed in its immediate vicinity The end of the temperature sensor of the power supply should be inserted between the two batteries which afterward...

Страница 21: ...diode of internal signalization yellow BAT 21 LED diode of internal signalization green MAINS Notes For each fault signal outputs there are 3 relay contacts available The description of the relay con...

Страница 22: ...he energized state The state of the relay can be tested for example with an ohmmeter applied between the appropriate outputs of its contacts After removing the interruption in the battery circuit the...

Страница 23: ...horized access to the interior of the cabinet Opening the cabinet door after opening the lock causes opening the sensor contacts and generating a fault signal flashing of the FAULT LED of the external...

Страница 24: ...eshold Reaction time 0 immediate reaction x the selected rows describe permanent states of operation preceding the start of the power supply LED signalization inside power supply PCB packet MAINS gree...

Отзывы: