AVTMST16 Rev 1 May 2016
28
Step Description
6
Select
to discharge the capacitor (only if
Measurement Start
option is set to
Manual
. See page 18.
Result:
A capacitor discharge (shot) is initiated.
If a breakdown / flashover takes place, the red fault trace typically has a strong negative
reflection. The red fault marker is automatically set to the position where both traces
diverge from each other.
NOTE:
If no trigger is received, no fault trace (red) is shown. Repeat the
procedure with a higher surge voltage (if possible) by selecting the
menu item.
If the blue trace (TDR trace) and the red trace are either 100%
matching or following each other very closely, the trigger has been
activated, however no breakdown/flashover was detected - increase
(
) voltage or possibly good cable.
7
If necessary, adjust the display settings, TDR settings and marker position through the
menu in order to identify the fault distance as precisely as possible. See page 38.
8
Select
to proceed with pinpointing or
to return to the main menu.