AVTMST16 Rev 1 May 2016
34
How to Pinpoint a Sheath Fault OR a Ground Fault in an
Unshielded Low Voltage Cable (both must be directly
buried)
Following a failed sheath test
(see page
Error! Bookmark not defined.
)
fault
location of the sheath fault in
direct buried cables
based on the step voltage
method (earth gradient method) can be performed with the SMART THUMP
serving as HV pulse generator (limited to a voltage of 5 kV, see below)
An
additional receiver
is required to read the strength and polarity of the earth
gradient voltage (e.g. Megger ESG-NT) in order to pinpoint the sheath fault.
When approaching the fault position, the step voltage increases quickly and
decreases to a zero reading directly over the fault and then will swing to a strong
voltage of the opposite polarity.
Proceed as follows to pinpoint the sheath fault:
Step Description
1
Select the
menu item from the
submenu.
2
Confirm the following two notices with
.
3
Adjust the surge voltage and select
to confirm the value.
4
Press the green illuminated “HV ON” button
.
5
Select
to start the sheath fault pinpointing mode. The
Voltage Selection, Automatic
should be disabled
(see page 18)
allowing you to select a voltage between 2 and 10 kV.
If the
Voltage Selection , Automatic
is enabled, the maximum voltage is limited to 4 kV,
Содержание SMART THUMP ST16
Страница 2: ...M ...
Страница 3: ...Portable Fault Locating System SMART THUMP ST16 User Manual ...
Страница 6: ...M M ...
Страница 10: ...M AVTMST16 Rev 1 May 2016 iv M ...
Страница 46: ...M AVTMST16 Rev 1 May 2016 36 M ...
Страница 52: ...M AVTMST16 Rev 1 May 2016 42 M ...
Страница 56: ...M AVTMST16 Rev 1 May 2016 46 ...
Страница 58: ...M AVTMST16 Rev 1 May 2016 48 M ...
Страница 60: ...M AVTMST16 Rev 1 May 2016 50 M ...
Страница 61: ...AVTMST16 Rev 1 May 2016 51 Appendix 1 Overview of TDR Features See next page for complete chart ...