3.8.4.4 Differential Relay Slope Test Results
This screen displays the results upon test completion. No data may be entered in this screen.
Figure 54 Differential Relay Slope Test
The bottom of the screen has common buttons.
File:
This selection will take the user to the File
Manager.
Batt Sim Off / Batt Sim On:
This selection will turn the Battery Simulator On
and Off.
Test Menu:
This selection will return the controller to the
Test Menu Screen.
Main Menu:
This selection will return the controller to the
Main Menu:
Start / Stop:
This selection will apply the set quantities
displayed and begin the test. After Start is
pressed this button will turn red and display
Stop. Pressing Stop at any time will stop the
test and turn the outputs off.
A timer setup link is available on this screen. Also the Timer Setup configuration is displayed for
convenience. The status of the relay contact will be displayed on the screen real time along with
the value of the current. The calculated Start and Stop current can also be seen on the test
screen. The Stop current is the maximum current provided by the test set before test is stopped.
This instance is applicable if the relay does not operate when ramping the current up between the
Start and Stop values. For this test two current channels will be used to energize the two restraint
coils of the relay. After the test is completed, the currents amplitude and the Actual Slope (%) will
be read out from the screen or stored in the memory.