3.8.10.3
Manual Auto Synchronizing Test Screen
Figure 97 Manual Synchronizing Test Screen
Description
The Manual Auto Synchronizing Test screen is designed to permit manual output control of the
MPRT and provide testing of synchronizing and auto synchronizing relays. This control screen
allows the user to apply any value of magnitude, phase angle, or frequency to a synchronizing
relay and time the response.
Operation
This screen can apply set values to visually watch the response of the relay, or the unit can apply
set values and start the timer and await a response time from a synchronizing relay.
Controls
V1...V4 & I1…I4:
Permits control of any installed voltage (V1, V2,
V3, V4) or current (I1, I2, I3, I4) generator.
Normally V1 and V2 are used to test
synchronizing type relays.
Mag:
Controls the Magnitude of any installed voltage
(V1, V2, V3, V4) or current (I1, I2, I3, I4)
generator.
Angle:
Controls the Phase Angle of any installed
voltage (V1, V2, V3, V4) or current (I1, I2, I3, I4)
generator.
-