The table below shows the available settings:
ETS-Text
Dynamic range
[default value]
Comment
Compass direction
clouding off
east
southeast
south
southwest
west
roof area
no azimuth evaluation
Adjustment of compass direction:
Clouding off:
Clouding is deactivated
Roof area:
Azimuth evaluation
possible from East
–
West
no azimuth evaluation:
Clouding
always active
Clouding active if azimuth
From
60°-300°
Azimuth angle from which the
shading is active
To
60°-300°
Azimuth angle until the shading is
active
Clouding active if elevation
From
2°-45
Angle of elevation from which the
shading is active
To
30°-90°
Angle of elevation until the shading
is active
Delay clouding On
1-30min
[2 min]
Delay until clouding is started after
overstepping the brightness
threshold
Delay clouding Off
5-60min
[15 min]
Delay to end clouding after the
brightness threshold has been
undercut
Release via
(temperature/set value)
not active
temperature value
temperature threshold
set value for heating
Setting whether automatic clouding
should only be released from a
certain temperature/control value of
the heating
Release if
temperature greater
than
15°C-35°C
[21°C]
Setting of a minimum temperature;
at "Release via
–
temperature value"
Release if
value 0
value 1
Setting of a threshold value;
at "Release via
–
threshold value"
Release if set value
for heating less than
0-50%
[5%]
Setting of a maximum control value;
at "Release via
–
control value for
heating"
Object clouding
not active
block at value 1
activate at value 1
block slat adjustment at
value 1
activate slat adjustment at
value 1
Activation of an object for
blocking/activation of clouding/slat
adjustment