4.10.1 Alarm Order (Priority)
The parameter "Alarm order" describes the priority of the individual alarms.
The following table shows the possible settings for this parameter:
ETS-Text
Dynamic range
[default value]
Comment
Alarm order
Wind alarm, Rain alarm, Frost alarm, Block function
Wind alarm, Rain alarm, Block function, Frost alarm
Wind alarm, Block function, Rain alarm, Frost alarm
Block function, Wind alarm, Rain alarm, Frost alarm
Indicates the priority
of the alarm function
Table 22: Setting option - Alarm order
If two or more alarms are active at the same time, the shutter actuator evaluates the alarms
according to the set sequence. The shutter actuator only performs the action of the higher priority
alarm. The action for the lower priority alarm is not executed as long as the higher priority alarm is
active. However, if the alarm with the higher priority is inactive and the lower priority alarm is still
active, then the action of the lower priority alarm is executed.