IOMM AGR-1
AGR 070A through 100A
89
Troubleshooting Analog Inputs
An analog input, such as a temperature sensor, is connected to the ADI board. The ADI board then
conditions the analog input. The conditioned input is transferred to the MCB via a ribbon cable.
Analog Input not Read by the MCB
If the MCB appears to be functioning properly and the analog input is not being read by the MCB,
perform the following procedure:
1.
Try cycling power to the controller by opening and then closing circuit breaker CB1.
2.
Check the ribbon cable, power wiring connector, and the field wiring connections from the
analog input device. Look for bent pins, cable on backwards, or mis-wires. Restore power after
reconnecting all cables and wires.
3.
If the problem persists, try swapping a known good ribbon cable or analog input device. Swap
these components separately to isolate the problem. Remove power from the controller before
disconnecting the suspect component, and restore power after connecting the replacement
component. If the problem persists, it is likely that the MCB is defective.
Troubleshooting Digital Inputs
A digital input device is connected to the ADI board. 24 Vac, supplied by transformer T2, is sent to
the digital input device via a supply wire. When a contact in the digital device makes, a return signal
is sent back to the ADI board. The ADI board then conditions the signal. The conditioned digital
input is then sent to the MCB via a ribbon cable.
Digital Input not Read by the MCB
If the MCB appears to be functioning properly and the digital input is not being read by the MCB,
perform the following procedure:
1.
Try cycling power to the controller by opening and then closing circuit breaker CB1.
2.
Check the ribbon cable, power wiring connector, and the field wiring connections from the digital
input device. Look for bent pins, cable on backwards, or mis-wires. Restore power after
reconnecting all cables and wires.
3.
If the problem persists, try swapping a known good ribbon cable or a digital input device. Swap
these components separately to isolate the problem. Remove power from the controller before
disconnecting the suspect component, and restore power after connecting the replacement
component. If the problem persists, it is likely that the MCB is defective.
Troubleshooting Output Boards
Each output on the Output Board consists of a solid-state relay, an LED, 5-amp fuse, and an MOV
(metal oxide varistor).
Normally, when the MCB commands an output to energize, the solid-state relay contacts will close
and the LED will glow. The contacts of each solid-state relay are in series with a 5-amp fuse. These
fuses resemble small resistors and are located on the board adjacent to the relays they serve. The
fuses are pressed into place. They can be removed with a needle nose pliers. The MOV, which is
located on the underside of the output board, protects the solid-state relay from high transient
voltages. MOVs are part of the output board and cannot be replaced.
Following are troubleshooting procedures for various symptoms of output board problems.
Note:
It should be possible to determine whether a solid-state relay is defective by using
these procedures.
Содержание AGR 070AS
Страница 20: ...20 AGR 070A through 100A IOMM AGR 1 Figure 9 Typical Field Wiring with Global UNT Controller...
Страница 21: ...IOMM AGR 1 AGR 070A through 100A 21 Figure 10 Typical Field Wiring Diagram with MicroTech Controller...
Страница 22: ...22 AGR 070A through 100A IOMM AGR 1 Figure 11 Standard Single Point Connection with FanTrol...
Страница 23: ...IOMM AGR 1 AGR 070A through 100A 23 Figure 12 Standard Single Point Connection with Optional SpeedTrol...
Страница 24: ...24 AGR 070A through 100A IOMM AGR 1 Figure 13 Unit Control Schematic 2 compressor UNT...
Страница 25: ...IOMM AGR 1 AGR 070A through 100A 25 Figure 14 Staging Schematic 2 compressor 4 stage UNT...
Страница 26: ...26 AGR 070A through 100A IOMM AGR 1 Figure 15 Staging Schematic 2 compressor 6 stage UNT...
Страница 27: ...IOMM AGR 1 AGR 070A through 100A 27 Figure 16 MicroTech Controller Schematic...
Страница 28: ...28 AGR 070A through 100A IOMM AGR 1 Figure 17 Unit Control Schematic MicroTech...
Страница 29: ...IOMM AGR 1 AGR 070A through 100A 29 Figure 18 Staging Schematic 4 stage MicroTech...
Страница 30: ...30 AGR 070A through 100A IOMM AGR 1 Figure 19 Staging Schematic 6 stage MicroTech...
Страница 31: ...IOMM AGR 1 AGR 070A through 100A 31 Figure 20 Unit Control Schematic 2 compressor MicroTech...
Страница 32: ...32 AGR 070A through 100A IOMM AGR 1 Figure 21 UNT Instrument Layout See legend on page 34...
Страница 33: ...IOMM AGR 1 AGR 070A through 100A 33 Figure 22 MicroTech Instrument Layout See legend on page 34...
Страница 35: ...IOMM AGR 1 AGR 070A through 100A 35 Figure 25 MicroTech Sensor Layout...
Страница 99: ...IOMM AGR 1 AGR 070A through 100A 99 Notes...
Страница 100: ...Post Office Box 2510 Staunton Virginia 24402 USA 800 432 1342 www mcquay com...