6
AGR 070A through 100A
IOMM AGR-1
Figure 3, Clearance Requirements
Do not block the flow of air to
and from the condenser coil.
Restricting airflow or allowing
air recirculation will result in a
decrease in unit performance
and efficiency because
discharge pressures are
increased. There must be no
obstruction above the unit that
would deflect discharge air
downward where it could be
recirculated back to the inlet of
the condenser coil. The
condenser fans are propeller
type and will not operate with
ductwork on the fan outlet.
Install the unit with enough side
clearance for air entrance to the
coil and for servicing. Provide
service access to the evaporator,
compressors, electrical control
panel and piping components.
Do not allow debris to
accumulate near the unit. Air
movement may draw debris into
the condenser coil causing coil
starvation. Give special
consideration to low ambient
operation where snow can
accumulate. Keep condenser
coils and fan discharge free of
snow or other obstructions to
permit adequate airflow for
proper unit operation.
The recommended minimum side clearance between two units is 10 feet (3048mm).
Distance less than 10 feet (3048mm) can result in air recirculation.
AIR
DISCHARGE
AIR
DISCHARGE
AIR
DISCHARGE
AIR
DISCHARGE
The minimum clearance to a side wall or building taller than the
Unit height is 6 feet (1828mm) provided no solid wall above 6 feet
(1830mm) tall is closer than 8 feet (2438mm) to the opposite
Side of the unit. (consult factory for special situations.)
The unit must not be installed in a pit or enclosure that is deeper
Or taller than the height of the unit unless extra space is provided,
(consult factory) the minimum clearance on each side of the unit is
8 feet (2438mm) when installed in a pit.
8 FT.
10 FT.
AIR FLOW
AIR FLOW
AIR FLOW
AIR FLOW
AIR FLOW
AIR FLOW
AIR FLOW
Содержание AGR 070AS
Страница 20: ...20 AGR 070A through 100A IOMM AGR 1 Figure 9 Typical Field Wiring with Global UNT Controller...
Страница 21: ...IOMM AGR 1 AGR 070A through 100A 21 Figure 10 Typical Field Wiring Diagram with MicroTech Controller...
Страница 22: ...22 AGR 070A through 100A IOMM AGR 1 Figure 11 Standard Single Point Connection with FanTrol...
Страница 23: ...IOMM AGR 1 AGR 070A through 100A 23 Figure 12 Standard Single Point Connection with Optional SpeedTrol...
Страница 24: ...24 AGR 070A through 100A IOMM AGR 1 Figure 13 Unit Control Schematic 2 compressor UNT...
Страница 25: ...IOMM AGR 1 AGR 070A through 100A 25 Figure 14 Staging Schematic 2 compressor 4 stage UNT...
Страница 26: ...26 AGR 070A through 100A IOMM AGR 1 Figure 15 Staging Schematic 2 compressor 6 stage UNT...
Страница 27: ...IOMM AGR 1 AGR 070A through 100A 27 Figure 16 MicroTech Controller Schematic...
Страница 28: ...28 AGR 070A through 100A IOMM AGR 1 Figure 17 Unit Control Schematic MicroTech...
Страница 29: ...IOMM AGR 1 AGR 070A through 100A 29 Figure 18 Staging Schematic 4 stage MicroTech...
Страница 30: ...30 AGR 070A through 100A IOMM AGR 1 Figure 19 Staging Schematic 6 stage MicroTech...
Страница 31: ...IOMM AGR 1 AGR 070A through 100A 31 Figure 20 Unit Control Schematic 2 compressor MicroTech...
Страница 32: ...32 AGR 070A through 100A IOMM AGR 1 Figure 21 UNT Instrument Layout See legend on page 34...
Страница 33: ...IOMM AGR 1 AGR 070A through 100A 33 Figure 22 MicroTech Instrument Layout See legend on page 34...
Страница 35: ...IOMM AGR 1 AGR 070A through 100A 35 Figure 25 MicroTech Sensor Layout...
Страница 99: ...IOMM AGR 1 AGR 070A through 100A 99 Notes...
Страница 100: ...Post Office Box 2510 Staunton Virginia 24402 USA 800 432 1342 www mcquay com...