AGR 070A through 100A
IOMM AGR-1
Lvg Low Lim SP
- Adjustable from 20°F - 40°F (default is 20°F). This safety that will shut the
chiller off based on the leaving water temperature going below this setpoint.
SoftSta Capcty
- Adjusts the ramping of steps from 0% - 100% (default is 50%).
SoftStart Time
- Adjustable ramping time from 0 - 20 minutes (default is 2 minutes).
Cir #1 Starts
- Counts the number of starts for circuit #1.
Cir #2 Starts
- Counts the number of starts for circuit #2. Note: If power is lost to the controller, this
data is lost and will start counting over. When power is applied and kept on, the controller will
allow 10 starts for circuit #1 as the lead circuit, then will switch to circuit #2 for the next 10
starts, etc (Automatic Lead/Lag).
Occupied
- |= On, 0 = Off
Flow Failure
- |= Alarm, 0 = Normal
OA Lockout
- Indicates whether your in OA lockout (see OA Lockout SP). No alarm.
Cir#2Lead=On
- Indicates which circuit is in the lead e.g., ½= On, 0 = Off indicates that circuit #2 is
in the lead.
Pmp/Stp #1=0
- |= Auto, circuit #1 allowed to run if cooling capacity is needed, 0 = Pump down
circut #1 and stop.
Pmp/Stp #2=0
- |= Auto, circuit #2 allowed to run if cooling capacity is needed, 0 = Pump down
circut #2 and stop.
Solenoid #1
- On a call for cooling on circuit 1, the solenoid is energized and opened.
Solenoid #2
- On a call for cooling on circuit 2, the solenoid is energized and opened.
Frzstat#1Alm
- If circuit #1 fails on freeze, the alarm light on the ZT will light. To clear the alarm,
the Freez-Stat Reset button (located on the Control Panel) must be pushed once to clear.
Frzstat#2Alm
- If circuit #2 fails on freeze, the alarm light on the ZT will light. To clear the alarm,
the Freez-Stat Reset button (located on the Control Panel) must be pushed once to clear.
MinLowPres#1
- If circuit #1 falls below the Minimum Low Pressure Setpoint (default is 10 psig) -
Differential (default is 5 psig) the ZT alarm will light. Once it increases above the Minimum
Low Pressure Setpoint, the alarm will clear.
MinLowPres#2
- If circuit #2 falls below the Minimum Low Pressure Setpoint (default is 10 psig) -
Differential (default is 5 psig) the ZT alarm will light. Once it increases above the Minimum
Low Pressure Setpoint, the alarm will clear.
Compressor #1
- Compressor 1 is On or Off
Compressor #2
- Compressor 2 is On or Off
Stage 3 to 6
- Indicates how many additional unloading stages are on at the time.
Содержание AGR 070AS
Страница 20: ...20 AGR 070A through 100A IOMM AGR 1 Figure 9 Typical Field Wiring with Global UNT Controller...
Страница 21: ...IOMM AGR 1 AGR 070A through 100A 21 Figure 10 Typical Field Wiring Diagram with MicroTech Controller...
Страница 22: ...22 AGR 070A through 100A IOMM AGR 1 Figure 11 Standard Single Point Connection with FanTrol...
Страница 23: ...IOMM AGR 1 AGR 070A through 100A 23 Figure 12 Standard Single Point Connection with Optional SpeedTrol...
Страница 24: ...24 AGR 070A through 100A IOMM AGR 1 Figure 13 Unit Control Schematic 2 compressor UNT...
Страница 25: ...IOMM AGR 1 AGR 070A through 100A 25 Figure 14 Staging Schematic 2 compressor 4 stage UNT...
Страница 26: ...26 AGR 070A through 100A IOMM AGR 1 Figure 15 Staging Schematic 2 compressor 6 stage UNT...
Страница 27: ...IOMM AGR 1 AGR 070A through 100A 27 Figure 16 MicroTech Controller Schematic...
Страница 28: ...28 AGR 070A through 100A IOMM AGR 1 Figure 17 Unit Control Schematic MicroTech...
Страница 29: ...IOMM AGR 1 AGR 070A through 100A 29 Figure 18 Staging Schematic 4 stage MicroTech...
Страница 30: ...30 AGR 070A through 100A IOMM AGR 1 Figure 19 Staging Schematic 6 stage MicroTech...
Страница 31: ...IOMM AGR 1 AGR 070A through 100A 31 Figure 20 Unit Control Schematic 2 compressor MicroTech...
Страница 32: ...32 AGR 070A through 100A IOMM AGR 1 Figure 21 UNT Instrument Layout See legend on page 34...
Страница 33: ...IOMM AGR 1 AGR 070A through 100A 33 Figure 22 MicroTech Instrument Layout See legend on page 34...
Страница 35: ...IOMM AGR 1 AGR 070A through 100A 35 Figure 25 MicroTech Sensor Layout...
Страница 99: ...IOMM AGR 1 AGR 070A through 100A 99 Notes...
Страница 100: ...Post Office Box 2510 Staunton Virginia 24402 USA 800 432 1342 www mcquay com...