52
1. Field Maintenance
Electrical Circuit
Possible causes of trouble
Power failure
Blown fuse or varistor
Loose connecons
Shorted or broken wires
Safety device opens
Faulty thermostat / room temperature
sensor
Wrong seng place of temperature sensor
Faulty transformer
Shorted or open capacitor
Faulty magnec contactor for compressor
Faulty magnec contactor for fan
Low voltage
Faulty stepping motor
Shorted or grounded compressor
Shorted or grounded fan motor
Unit will not start
Compressor will not start but
fans run
Compressor and condenser
(outdoor) fan will not start
Evaporator (indoor) fan will not
start
Condenser (Outdoor) fan will
not start
Unit runs, but shortly stops
Compressor short-cycles due
to overload
High discharge pressure
Low discharge pressure
High sucon pressure
Low sucon pressure
Unit runs connuously but insuf-
ficient cooling
Too cool
Compressor is noisy
Horizontal louver can not
revolve
Test method / remedy
Test voltage
Inspect fuse type & size
Inspect connecons - tighten
Test circuits with tester
Test connuity of safety device
Test connuity of thermostat / sensor
& wiring
Place the temperature sensor at the
central of the air inlet grille
Check control circuit with tester
Check capacitor with tester
Test connuity of coil & contacts
Test connuity of coil & contacts
Test voltage
Replace the stepping motor
Check resistance with mulmeter
Check resistance with mulmeter