“Wall” Type Active Line R32 Refrigerant AC: 6. Troubleshooting
[6]-31
YES
YES
NO
NO
YES
YES
Replace high pressure protector.
Stop the unit.
Is the heat exchanger dirty?
Clean the heat exchanger.
High pressure protection.
Are the high pressure switch
and main control board wired
correctly?
Connect high pressure switch
and main control board.
Is the high pressure
protector broken?
NO
NO
Method: Disconnect the plug.
Measure the resistance of the
high pressure protector, if the
protector is normal the value is
0. Does a problem still exist?
Is the outdoor ambient tempera-
ture higher than 50°C?
Check if the outdoor unit venti-
lation is good.
Ensure that the outdoor unit ventilation
is functioning properly.
Is the outdoor fan running properly?
NO
Please refer to the solution of the
“Fan speed is operating outside of
normal range” malfunction.
YES
YES
NO
Replace outdoor main board.
Is the problem solved?
NO
Check whether the refrigerant
system is functioning properly.