46
8.0 Troubleshooting
8.1 Safety caution
WARNING
Be sure to turn off all power supplies or disconnect all wires to avoid electric shock.
While checking indoor/outdoor PCB, please equip yourself with antistatic gloves or wrist
strap to avoid damage to the board.
WARNING
Electricity remains in capacitors even when the power supply is off. Ensure the capaci-
tors are fully discharged before troubleshooting.
Test the voltage between P and N on back of the main PCB with multimeter. If the voltage is 36V, the
capacitors are fully discharged.
Note: This picture is for reference only. Actual appearance may vary.
8.2 General troubleshooting
8.2.1 Error Display (Indoor Unit)
When the Indoor Unit encounters a recognized error, the Operation Lamp will flash in a corresponding
series, the Timer Lamp may turn ON or begin flashing, and an error code will be displayed. These error
codes are described in the following table:
Operation Lamp
Timer Lamp
Display Error information
1 time
OFF
E0
Indoor unit EEPROM parameter error.
2 times
OFF
E1
Indoor / outdoor unit communication error.
3 times
OFF
E2
Zero-crossing signal detection error (for some models).
4 times
OFF
E3
The indoor fan speed is operating outside of the normal range.
5 times
OFF
E4
Indoor room temperature sensor T1 is in open circuit or has short circuit.
6 times
OFF
E5
Evaporator coil temperature sensor T2 is in open circuit or has short circuit.
9 times
OFF
E7
Indoor PCB / Display board communication error (for some models).
7 times
OFF
EC
Refrigerant leak detected.
1 time
ON
F0
Current overload protection.
2 times
ON
F1
Outdoor temperature sensor T4 is in open circuit or has short circuit.