2. In the
PLC/Controller Address
frame, enter the
PLC coil
or
controller address
. Or click the
PLC/Controller Address button
to display the Edit PLC/Controller Address dialog box:
3. In the reference address area, click the pull-down box to select the
target PLC memory area
. Use the
numeric keypad to enter the specific
PLC memory address
. Select the
PLC Network Address
(if
applicable) and
HMI communications port
. Click
Enter
to go back to prior dialog box.
4. In the
Format
attribute box, select the
format type
you wish to use. The options are:
Format
Range
Size
(Bits)
Description
Unsigned
0 to 65535
16
unsigned 16 bit format
0 to 4294967295
32
unsigned 32 bit format
Signed
-
32768 to +32767
16
signed 16 bit format
-2147483648 to +2147483647
32
signed 32 bit format
Hexadecimal
0000 to FFFF
16
hexadecimal 16 bit format
00000000 to FFFFFFFF
32
hexadecimal 32 bit format
BCD
0000 to 9999
16
BCD 16 bit format
00000000 to 99999999
32
BCD 32 bit format
ASCII
Printable characters
16
2 ASCII characters
Printable characters
32
4 ASCII characters
Binary
00… to 11… (16 bits)
16 only
binary 16 bit format
Floating
-21474836 to +2147483648
32 only
floating 32 bit only
5. In the
Size
attribute box, select either
16 bits
or
32 bits
.
6. In the
Alignment
attribute box, select how you wish to
align
the data that is displayed: left
justification, right justification, or centered.
7. The
Int. Number
and
Dec. Number
attribute boxes are used to specify the number of digits you want
displayed before/after a decimal point. For example, if you are monitoring a 16-bit PLC register
(+220) using signed format and have Int.Number =2 and Dec.Number =1, then the BLU300 displays
this number as +22.0.
*
If the value in the PLC register requires more digits than you have allocated with the Int.
Number and Dec. Number, the HMI will only display the specified digits. For example, if the
value in the PLC register is +17,220 and Int.Number = 2 and Dec. Number = 1, then the HMI
will d22.0 giving no indication that the actual value in the PLC register is larger.
1010-0300, Rev 02
96
Blue Series Installation & Operation Manual
Содержание BLU300 Series
Страница 1: ......
Страница 64: ...1010 0300 Rev 02 62 Blue Series Installation Operation Manual...
Страница 113: ...1010 0300 Rev 02 112 Blue Series Installation Operation Manual...
Страница 138: ...Appendix B Dimensional Outlines Panel Cutout 1010 0300 Rev 02 Dimensional Outlines Panel Cutout 141...