To configure the System Parameter Setting to display a screen
1. From the Global Settings menu, select
System Parameter Setting
. The System Parameter Editor
dialog appears.
2. In the PLC/Controller Address frame, enter the
PLC/register address,
or click the PLC/Controller
Address button
to display the address dialog.
3. Click the pull-down box to select the
target PLC memory area.
Use the numeric keypad to enter the
specific
PLC memory address.
Select the
PLC Network Address
(if applicable) and
HMI
communications port.
Click
Enter
to go back to prior dialog box.
4. Click
Set
to enable the System Parameter Setting,
Cancel Set
to disable the System Parameter Setting,
or
Close
to exit the System Parameter Editor window and return to the work area.
The OIT will now monitor that address. If the PLC writes a value (16-bit Signed) into this register, the OIT will attempt to
display the screen. If the screen does not exist, the OIT will continue to display the existing screen. If a new screen is
displayed, the OIT will write a value of -1 into the register after it has displayed the new screen.
*
If this feature is enabled, the "Jump to Screen" feature will no longer be available.