ECODRIVE DKC01.1/DKC11.1 Drive Controllers
ECODRIVE DKC drive controllers
4-23
DOK-ECODRV-DKC01/11.1*-PRJ3-EN-P
•
Logical 1 is recognized if a positive differential voltage is applied from
SM+ to SM-.
•
Logical 0 is recognized if a negative differential voltage is applied from
SM+ to SM-.
•
To increase noise immunity, the differential voltage range should be at
least 2.5 volts. The greater the differential voltage range, the higher
the operational reliability against interference.
AP0219.fh5
Control unit
0 Vext
C
+
max. 20 m
0V
1
2
3
4
5
6
7
8
9
10
11
12
SM1+
SM1-
SM2+
SM2-
X2
min.
Clock frequency
Inputs:
max.
Input voltage
0 V
30 V
max. 175 kHz
+
-
2k
4k
+15 V
+5 V
+15 V
+5 V
200
200
2k
2k
2k
50k
22p
SM+
SM-
Channel
Channel
Channel
-
-
Fig. 4-31: Control with differential signals
Control with differential signals