ECODRIVE DKC01.1/DKC11.1 Drive Controllers
NFD / NFE line filter
8-3
DOK-ECODRV-DKC01/11.1*-PRJ3-EN-P
The mounting plate or the control cabinet housing to which the DKC is
mounted are the preferred locations for assembly.
DANGER
Live parts (greater than 50 V)!
Electric shock on contact!
⇒
Before startup operation, the protective ground con-
ductor must first be permanently connected to the fil-
ter and then grounded!
⇒
Before touching bare connection lines and terminals,
isolate the filter with the connected terminals or dis-
connect it. Allow time for discharging! Do not work on
connecting cables until then!
⇒
Due to the high discharge current of the filter, opera-
tion is not permitted without a connected protective
conductor!
⇒
This is why the filter may only be operated with a per-
manently connected protective conductor with a cross
section
≥
10 mm
2
!
⇒
Remove any paint or coatings from the mounting
points of the filter.
⇒
Use a tooth-lock washer with galvanized or tin-plated
screws.
8.3 Electrical
connection
To assemble and install the line filters, observe the recommendations in
the documents
"EMC in Drive and Control Systems"
- Project Planning Manual -
central grounding
point within
control enclosure
fuse
power supply
master switch
fuse
control voltage
mains contactor
NFE mains filter
1) The use of switch-mode power sections (NTM) requires
the preliminary switching of the NFE 01.1-230-006 mains filter
2) Mounting on mounting panel of DKC is recommended
Control voltage
connection for DKC X4
Mains connection
X8
A03DCC1P.fh5
Q10
Q2
NTM
Q1
K1
L1
N
PE
1 x AC 230 V
+10% -15%
(50-60 Hz)
Q1 :
Q10:
Q2 :
K1 :
=
LINE
LOAD
L1
N
PE
L1'
N'
PE'
NFE01.1
-230-006
V+
V-
N
L
1)
2)
Protective conductor
connection
≥
10mm
2
mains filter
Fig. 8-4: Single-phase line filter connection with NFE02.1-230-008
Notes on assembly