ECODRIVE DKC01.1/DKC11.1 Drive Controllers
Power connection
11-5
DOK-ECODRV-DKC01/11.1*-PRJ3-EN-P
11.4 Protection against indirect contact
As a result of the high capacitive leakage currents via the cable insulation,
it is not possible to install a GFCB device in the power input line
(compliant to DIN VDE 0160, section 6.5).
Thus, protection against indirect contact must be achieved by other
means.
The drive system components have a protective grounded housing. This
makes protection against indirect contact possible by grounding.