Electrical System
Section 6
6-34
Part No. 80-1214-3
QF2300
Automatic Shut-Off
3B. WATER DRAIN
To allow water to drain from the
evaporator, the dump valve energizes
for 90 seconds, then de-energizes.
An 8 minute lockout starts when the
compressor de-energizes. When the
ice drops away from the bin level
probe the ice machine will begin an
initial start-up cycle, provided the “8
minute lockout” has expired.
SV2112
RELAY
K1
RELAY
K2
RELAY
K3
RELAY K4
(25)
L1
L2
(54)
(53)
LIQUID LINE
SOLENOID
CENTRIFUGAL
SWITCH
(65)
INTERNAL
OVERLOAD
START
RUN
GEARMOTOR
WATER FLOAT
VALVE
DUMP VALVE
(56)
(55)
(22)
(51)
(52)
7 AMP
FUSE
GROUND
(58)
(57)
EQUALIZATION
SOLENOID
C2
C1
(91)
(22)
3B. Water Drain
(90 Seconds)
Toggle Switch
ICE
Bin Level Probe
CLOSED ( Ice Contacting probe)
Control Board Relays
#1
Liquid Line Solenoid Valve
OFF
#2
Dump Valve
ON
#3
Gear Motor
OFF
#$
Water Float Valve Solenoid Coil
OFF
Revised 8/2003
Содержание QC0700
Страница 8: ...Table of Contents continued 6 Part No 80 1214 3 Revised 8 2003 ...
Страница 12: ...General Information Section 1 1 4 Part No 80 1214 3 THIS PAGE INTENTIONALLY LEFT BLANK Revised 8 2003 ...
Страница 30: ...Installation Instructions Section 2 2 18 Part No 80 1214 3 THIS PAGE INTENTIONALLY LEFT BLANK Revised 8 2003 ...
Страница 52: ...Ice Machine Sequence of Operation Section 4 4 4 Part No 80 1214 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 122: ...Electrical System Section 6 6 60 Part No 80 1214 3 THIS PAGE INTENTIONALLY LEFT BLANK Revised 8 2003 ...
Страница 144: ...Refrigeration System Section 7 7 22 Part No 80 1214 3 Using Pinch Off Tool SV1406 Revised 8 2003 ...
Страница 147: ...Revised 8 2003 ...
Страница 150: ...Refrigeration System Section 7 7 26 Part No 80 1214 3 THIS PAGE INTENTIONALLY LEFT BLANK Revised 8 2003 ...