Electrical System
Section 6
6-30
Part No. 80-1214-3
QF2300 Ice Machine Head Section
Freeze Cycle
2. FREEZE
When water contacts the water level
probe the liquid line solenoid valve,
equalization valve, compressor and
condenser fan motor energize. The
gear motor, compressor, condenser
fan motor and water float valve
solenoid remain energized as the ice
machine makes ice. The water float
valve will open and close
automatically to maintain the proper
water level.
SV2111
RELAY
K1
RELAY
K2
RELAY
K3
RELAY K4
(25)
L1
L2
(54)
(53)
LIQUID LINE
SOLENOID
CENTRIFUGAL
SWITCH
(65)
INTERNAL
OVERLOAD
START
RUN
GEARMOTOR
WATER FLOAT
VALVE
DUMP VALVE
(56)
(55)
(22)
(51)
(52)
7 AMP
FUSE
GROUND
(58)
(57)
EQUALIZATION
SOLENOID
C2
C1
(91)
(22)
2. Freeze
(Until Ice Contacts Bin Level Probe for 30 Continuous Seconds)
Toggle Switch
ICE
Bin Level Probe
Open (No Ice Contact)
Control Board Relays
#1
Liquid Line Solenoid Valve
ON
#2
Dump Valve
OFF
#3
Gear Motor
ON
#4
Water Float Valve Solenoid Coil
ON
Revised 8/2003
Содержание QC0700
Страница 8: ...Table of Contents continued 6 Part No 80 1214 3 Revised 8 2003 ...
Страница 12: ...General Information Section 1 1 4 Part No 80 1214 3 THIS PAGE INTENTIONALLY LEFT BLANK Revised 8 2003 ...
Страница 30: ...Installation Instructions Section 2 2 18 Part No 80 1214 3 THIS PAGE INTENTIONALLY LEFT BLANK Revised 8 2003 ...
Страница 52: ...Ice Machine Sequence of Operation Section 4 4 4 Part No 80 1214 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 122: ...Electrical System Section 6 6 60 Part No 80 1214 3 THIS PAGE INTENTIONALLY LEFT BLANK Revised 8 2003 ...
Страница 144: ...Refrigeration System Section 7 7 22 Part No 80 1214 3 Using Pinch Off Tool SV1406 Revised 8 2003 ...
Страница 147: ...Revised 8 2003 ...
Страница 150: ...Refrigeration System Section 7 7 26 Part No 80 1214 3 THIS PAGE INTENTIONALLY LEFT BLANK Revised 8 2003 ...