Section 6
Electrical System
Part No. 80-1214-3
6-25
QF2200
Automatic Shut-Off
An 8 minute lockout starts when the
compressor de-energizes. When the
ice drops away from the bin level
probe the ice machine will begin an
initial start-up cycle, provided the “8
minute lockout” has expired.
8 Minute Lockout
The bin level light will flash until the 8
minute lockout expires. After the 8
minute lockout time can be
overridden by moving the ON/OFF/
CLEAN toggle switch for ICE to OFF
and back to ICE.
SV3048
RELAY
K1
RELAY
K2
RELAY
K3
RELAY K4
(25)
L1
L2
(54)
(53)
LIQUID LINE
SOLENOID
CENTRIFUGAL
SWITCH
(65)
INTERNAL
OVERLOAD
START
RUN
GEARMOTOR
WATER FLOAT
VALVE COIL
DUMP VALVE
COIL
(56)
(55)
(22)
(51)
(52)
7 AMP
FUSE
GROUND
Automatic Shut-Off
(Until Ice No Longer Contacts Bin Level Probe)
Toggle Switch
ICE
Bin Level Probe
CLOSED ( Ice Contacting probe)
Control Board Relays
#1
Liquid Line Solenoid Valve
OFF
#2
Dump Valve
OFF
#3
Gear Motor
OFF
#$
Water Float Valve Solenoid Coil
OFF
Revised 8/2003
Содержание QC0700
Страница 8: ...Table of Contents continued 6 Part No 80 1214 3 Revised 8 2003 ...
Страница 12: ...General Information Section 1 1 4 Part No 80 1214 3 THIS PAGE INTENTIONALLY LEFT BLANK Revised 8 2003 ...
Страница 30: ...Installation Instructions Section 2 2 18 Part No 80 1214 3 THIS PAGE INTENTIONALLY LEFT BLANK Revised 8 2003 ...
Страница 52: ...Ice Machine Sequence of Operation Section 4 4 4 Part No 80 1214 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 122: ...Electrical System Section 6 6 60 Part No 80 1214 3 THIS PAGE INTENTIONALLY LEFT BLANK Revised 8 2003 ...
Страница 144: ...Refrigeration System Section 7 7 22 Part No 80 1214 3 Using Pinch Off Tool SV1406 Revised 8 2003 ...
Страница 147: ...Revised 8 2003 ...
Страница 150: ...Refrigeration System Section 7 7 26 Part No 80 1214 3 THIS PAGE INTENTIONALLY LEFT BLANK Revised 8 2003 ...